D1053 

- SIL 2 Analog Signal Converter and Trip Amplifiers 

G.M. International ISM0016-13 

D1053 is an isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/ Non Hazardous Locations or Zone 2, Group IIC, 
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous 
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, 
and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1053 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1053 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock 
when connected to live hazardous potential

Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. The unit cannot be repaired by the end user and must be returned to the 
manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

Operation 

 

Input channel of D1053 accepts a current or voltage signal from Hazardous Area/Hazardous Locations from separately powered 3, 4 wire transmitter, voltage or current source, and 
repeats or converts the current or voltage to a 0/4-20 mA or 0/1-5 V or 0/2-10 V floating output to drive a load in Safe Area/Non Hazardous Locations. In addition to the analog output the 
barrier has also a two channel trip amplifiers providing two relay SPST contacts, alarm A and B, that can be configured as HIGH, LOW, LOW start-up, BURNOUT alarm operating mode 
and NE or ND relay operating mode. Presence of supply power is displayed by a green signaling LED, status of alarm output A and B is displayed by two red LED. 

 

D1053 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Intrinsically 

Safe Equipment

Must not use or generate

more than 250 Vrms or Vdc

Control 

Equipment

Unclassified Locations

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

Non-incendive 

Equipment

Unclassified Locations

14
15

1
2

+

-

+
+

-

+

Power Supply

3
4

Must not use or generate

more than 250 Vrms or Vdc

16

-

+

-

+

Control 

Equipment

6

5

15
16

14

D1053 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Control 

Equipment

7
8

-

+

-

+

Control 

Equipment

Power Supply

Control 

Equipment

Control 

Equipment

2

3
4

8

7

5
6

1

Содержание D1053S

Страница 1: ...D1053 SIL 2 Analog Signal Converter and Trip Amplifiers ISM0016 13 D1053S INSTRUCTION MANUAL SIL 2 Analog Signal Converter and Trip Amplifiers Din Rail Model D1053S ...

Страница 2: ...ripple 20 mVrms on 250 Ω load Alarm Trip point range within rated limits of input sensor see input for step resolution Delay time 0 to 1000 s 100 ms step Hysteresis 0 to 5 mA on current or 0 to 5 V on voltage see input for step resolution Output voltage free SPST relay contact Contact rating 2 A 250 Vac 500 VA 2 A 250 Vdc 80 W resistive load Performance Ref Conditions 24 V supply 250 Ω load 23 1 C...

Страница 3: ...inear or reverse Two independent trip amplifiers Output for burnout detection High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 Fully programmable operating parameters ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD componen...

Страница 4: ...4 15 16 Io Isc 4 mA Ch1 14 15 16 Po Po 11 mW Ch1 14 15 16 Ii Imax Pi Pi D1053 Terminals Ch1 14 15 16 Ch1 14 15 16 Ch1 14 15 16 D1053 Associated Apparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 135 µF Co Ca 14 995 µF Co Ca 65 995 µF IIB C IIA D IIC A B Lo La 2541 mH Lo La 10167 mH Lo La 20335 mH IIB C IIA D IIC A B Lo Ro 3520 µH Ω Lo Ro...

Страница 5: ... 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 I Signal 5 6 7 8 Alarm A Alarm B Set A Set B MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 V Signal 5 6 7 8 Alarm A Alarm B Set A Set B For SIL applications alarm contacts ...

Страница 6: ...when connected to live hazardous potential Explosion Hazard to prevent ignition of flammable or combustible atmospheres disconnect power before servicing or unless area is known to be nonhazardous Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury The unit cannot be repaired by the end user and must be returned to the manufacturer or his ...

Страница 7: ...tional installation standards e g EN IEC60079 14 Electrical apparatus for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Hazardous Classified Locations National Electrical Code NEC ANSI NFPA 70 Section 504 and 505 Canadian Electrical Code CEC make sure that conducto...

Страница 8: ... 12 V I dc mA dc input from externally powered transmitter range from 4 to 24 mA 8 Br LO 3 Level Menu Displays the burnout LOW trip point value configuration Press Enter to set the burnout condition trip point value below this value indicate a burnout fault condition set 5 000 to disable press the Select key to the next menu level item or Up key to return to second level If you pressed Enter key y...

Страница 9: ...n Press Enter to set the delay time value press the Select key to the next menu level item or Up key to return to third level If you pressed Enter key you can set the delay value 100 ms step press the Select key to highlight the character you want to change and then the Up and Down keys to select the number confirm the modification with the Enter key The value is settable from 0 to 1000 seconds in...

Отзывы: