8
D1010
- SIL 2 Repeater Power Supply Smart-Hart compatible
G.M. International ISM0007-16
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
CLASS I, ZONE 0, GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
Terminals 15-12
Uo/Voc = 2.2 V
Io/Isc = 38 mA
Po/Po = 21 mW
Connections for Duplication of Active Input Signals
Safety Description
Restriction on specifications for externally powered Transmitter:
The voltage drop must be changed in 1.8 V maximum
The safety parameters must be changed in: Uo/Voc = 2.2 V, Io/Isc = 38 mA, Po/Po = 21 mW
MODEL D1010D Duplicator
=
=
=
=
=
14
15
16
3 +
4 -
1
2
8
RL
mA
+
-
mA
+
V
Supply 24 Vdc
Source I
Source V
Sink I
Out 1-A
+
-
+
-
+
-
External
Powered Tx
In 1
=
=
=
=
=
10
11
12
5
6
7
RL
mA
+
-
mA
+
V
Source I
Source V
Sink I
Out 1-B
+
-
+
-
RL
RL
IIC
IIB
IIA
100
1000
1000
11.3
45.3
90.7
849
3396
6793
Group
Cenelec
Lo/Ro
(µH/
Ω
)
Lo/La
(mH)
Co/Ca
(µF)
(with 16-11 shorted)