D1010 

- SIL 2 Repeater Power Supply Smart-Hart compatible 

G.M. International ISM0007-16 

When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D1010 Associated Apparatus are not exceeded by 
the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below: 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter). 
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system 
when the above conditions are respected. 
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved); 
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved). 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D1010 Associated 

Apparatus Parameters 

Ui / Vmax = 30V 

Uo / Voc 

D1010 Terminals 

Ch1 

Ch2 

15 - 16 

11 - 12 

li / Imax = 104 mA 

Ch1 

Ch2 

15 - 16 

11 - 12 

 

Io / Isc 

 

Ci = 1.05 nF, Li= 0 nH 

Ch1 

Ch2 

15 - 16 

11 - 12 

Содержание D1010D

Страница 1: ...D1010 SIL 2 Repeater Power Supply Smart Hart compatible ISM0007 16 D1010S D1010D SIL 2 Repeater Power Supply Smart Hart compatible DIN Rail Models D1010S D1010D INSTRUCTION SAFETY MANUAL...

Страница 2: ...ad influence 0 05 of full scale for a 0 to 100 load resistance change Temperature influence 0 01 on zero and span for a 1 C change Compatibility CE mark compliant conforms to Directive 2014 34 EU ATEX...

Страница 3: ...omponents High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier...

Страница 4: ...uctance do not exceed the limits Co Ca Lo La Lo Ro given in the Associated Apparatus parameters for the effective gas group See parameters on enclosure side and the ones indicated in the table below D...

Страница 5: ...f the cable parameters are unknown the following value may be used Capacitance 60pF per foot 180pF per meter Inductance 0 20 H per foot 0 60 H per meter The Intrinsic Safety Entity Concept allows the...

Страница 6: ...E 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1010D 14 15 16 3 4 1 2 8 RL mA mA V HHT Supply 24 Vdc Source I Source V Sink I O...

Страница 7: ...Duplication of 2 wires Transmitter Input Safety Description Restriction on specifications for 2 wires Transmitter Input Bidirectional communication for Smart Transmitter is provided only on channel 1...

Страница 8: ...15 12 Uo Voc 2 2 V Io Isc 38 mA Po Po 21 mW Connections for Duplication of Active Input Signals Safety Description Restriction on specifications for externally powered Transmitter The voltage drop mus...

Страница 9: ...il Dangerous failure mode that does not respond to a demand from the process i e being unable to go to the defined Fail Safe state or deviates the output current by more than 5 0 8 mA of full span Fai...

Страница 10: ...ss Fail Dangerous failure mode that does not respond to a demand from the process i e being unable to go to the defined Fail Safe state or deviates the output current by more than 5 0 8 mA of full spa...

Страница 11: ...re than 5 0 8 mA of full span Fail High failure mode that causes the output signal to go above the maximum output current 20 mA Assuming that the application program in the Safety logic solver is conf...

Страница 12: ...l Safe state or deviates the output current by more than 5 0 8 mA of full span Fail High failure mode that causes the output signal to go above the maximum output current 20 mA Assuming that the appli...

Страница 13: ...be accomplished via conduit connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than...

Страница 14: ...hannel model the function and location of each connection terminal using the wiring diagram on the corresponding section as an example Connect 24 Vdc power supply positive at terminal 3 and negative a...

Страница 15: ...n Side A Panel View Span Trimmer CH1 Span Trimmer CH2 Screwdriver for Trimmers Calibration Trimmer Ch1 Calibration Trimmer Ch2 Dip switch configuration Turn the trimmer clockwise to Increase Output va...

Страница 16: ...e reading in DC supply 20 mA range at terminals 1 and 2 Execute the next test to verify D1010S unit channel or execute it twice to verified both D1010D unit channels Verify that green led on the front...

Отзывы: