D1010
- SIL 2 Repeater Power Supply Smart-Hart compatible
G.M. International ISM0007-16
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D1010 Associated Apparatus are not exceeded by
the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable),
then 50 % of Co and Lo parameters are applicable and shall not be exceeded
(50 % of the Co and Lo become the limits which must include the cable such that
Ci C cable
≤
50 % of Co and Li L cable
≤
50 % of Lo).
If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter).
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system
when the above conditions are respected.
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved);
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved).
Must
be
Hazardous Area/
Hazardous Locations
Device Parameters
D1010 Associated
Apparatus Parameters
Ui / Vmax = 30V
Uo / Voc
D1010 Terminals
Ch1
Ch2
15 - 16
11 - 12
li / Imax = 104 mA
Ch1
Ch2
15 - 16
11 - 12
≥
Io / Isc
≥
Ci = 1.05 nF, Li= 0 nH
Ch1
Ch2
15 - 16
11 - 12