background image

 

D1010 

- SIL 2 Repeater Power Supply Smart-Hart compatible 

G.M. International ISM0007-16 

Model:  

D1010 

1 channel 

Power Bus enclosure 

2 channels 

/B 

 

Ordering information 

 

Front Panel and Features 

 



SIL 2 according to IEC 61508:2010 Ed. 2 for  Tproof = 7 / 10 years (

10% / >10 % of total SIF) with active input. 



SIL 2 according to IEC 61508:2010 Ed. 2 for Tproof = 6 / 10 years (

10% / >10 % of total SIF) with passive input. 



PFDavg (1 year) 1.30 E-04, SFF 80.51 % with active input. 



PFDavg (1 year) 1.47 E-04, SFF 80.81 % with passive input. 



SIL 3 Systematic capability. 



Input from Zone 0 (Zone 20), Division 1, 

installation in Zone 2, Division 2. 



4-20 or 0-20 mA Input, Output Signal. 



Wide Band Smart Communication, 

Hart compatible. 



Input and Output short circuit proof. 



High Accuracy. 



Three port isolation, Input/Output/Supply. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1  



In-field programmability by DIP Switch. 



ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, TÜV Certifications. 



TÜV Functional Safety Certification. 



Type Approval Certificate DNV and KR for maritime applications. 



High Reliability, SMD components. 



High Density, two channels per unit. 



Simplified installation using standard DIN Rail and plug-in terminal blocks. 



250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier. 

Not used 

Terminal block connections 

HAZARDOUS AREA 

SAFE AREA 

+ Input Ch 2 for 2 wire Transmitters 

- Input Ch 2 for 2 wire Transmitters or  
+ Input Ch 2 for External Powered Transmitters 

- Input Ch 2 for External Powered Transmitters 

Not used 

+ Input Ch 1 for 2 wire Transmitters 

- Input Ch 1 for 2 wire Transmitters or 
+ Input Ch 1 for External Powered Transmitters 

- Input Ch 1 for External Powered Transmitters 

9

 

10

 

11

 

12

 

13

 

14

 

15

 

16

 

+ Output Ch 1 for Current Source mode or 
+ Output Ch 1 for Voltage Source mode 

1

 

- Output Ch 1 for Current Source mode or - Output Ch 1 for 
Voltage Source mode or + Output Ch 1 for Current Sink mode 

2

 

+ Power Supply 24 Vdc 

3

 

- Power Supply 24 Vdc 

4

 

+ Output Ch 2 for Current Source mode or 
+ Output Ch 2 for Voltage Source mode 

5

 

- Output Ch 2 for Current Source mode or - Output Ch 2 for  
Voltage Source mode or + Output Ch 2 for Current Sink mode 

6

 

- Output Ch 2 for Current Sink mode 

7

 

- Output Ch 1 for Current Sink mode 

8

 

Power Bus and DIN-Rail accessories: 
DIN rail anchor MCHP065   

DIN rail stopper MOR016 

Terminal block male MOR017 

Terminal block female MOR022 

Содержание D1010D

Страница 1: ...D1010 SIL 2 Repeater Power Supply Smart Hart compatible ISM0007 16 D1010S D1010D SIL 2 Repeater Power Supply Smart Hart compatible DIN Rail Models D1010S D1010D INSTRUCTION SAFETY MANUAL...

Страница 2: ...ad influence 0 05 of full scale for a 0 to 100 load resistance change Temperature influence 0 01 on zero and span for a 1 C change Compatibility CE mark compliant conforms to Directive 2014 34 EU ATEX...

Страница 3: ...omponents High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier...

Страница 4: ...uctance do not exceed the limits Co Ca Lo La Lo Ro given in the Associated Apparatus parameters for the effective gas group See parameters on enclosure side and the ones indicated in the table below D...

Страница 5: ...f the cable parameters are unknown the following value may be used Capacitance 60pF per foot 180pF per meter Inductance 0 20 H per foot 0 60 H per meter The Intrinsic Safety Entity Concept allows the...

Страница 6: ...E 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1010D 14 15 16 3 4 1 2 8 RL mA mA V HHT Supply 24 Vdc Source I Source V Sink I O...

Страница 7: ...Duplication of 2 wires Transmitter Input Safety Description Restriction on specifications for 2 wires Transmitter Input Bidirectional communication for Smart Transmitter is provided only on channel 1...

Страница 8: ...15 12 Uo Voc 2 2 V Io Isc 38 mA Po Po 21 mW Connections for Duplication of Active Input Signals Safety Description Restriction on specifications for externally powered Transmitter The voltage drop mus...

Страница 9: ...il Dangerous failure mode that does not respond to a demand from the process i e being unable to go to the defined Fail Safe state or deviates the output current by more than 5 0 8 mA of full span Fai...

Страница 10: ...ss Fail Dangerous failure mode that does not respond to a demand from the process i e being unable to go to the defined Fail Safe state or deviates the output current by more than 5 0 8 mA of full spa...

Страница 11: ...re than 5 0 8 mA of full span Fail High failure mode that causes the output signal to go above the maximum output current 20 mA Assuming that the application program in the Safety logic solver is conf...

Страница 12: ...l Safe state or deviates the output current by more than 5 0 8 mA of full span Fail High failure mode that causes the output signal to go above the maximum output current 20 mA Assuming that the appli...

Страница 13: ...be accomplished via conduit connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than...

Страница 14: ...hannel model the function and location of each connection terminal using the wiring diagram on the corresponding section as an example Connect 24 Vdc power supply positive at terminal 3 and negative a...

Страница 15: ...n Side A Panel View Span Trimmer CH1 Span Trimmer CH2 Screwdriver for Trimmers Calibration Trimmer Ch1 Calibration Trimmer Ch2 Dip switch configuration Turn the trimmer clockwise to Increase Output va...