![Glowworm Energy 35 Store-A Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/glowworm/energy-35-store-a/energy-35-store-a_installation-and-maintenance-instructions-manual_2234641034.webp)
Appendix
34
Installation and maintenance instructions Energy 0020201109_01
11
Ignition and flame control electrode
12
Temperature sensor in the heating flow
13
Temperature sensor in the heating return
14
Gas valve
15
Fan
16
Temperature sensor in the cylinder
17
Temperature sensor in the heat exchanger
18
Diverter valve
19
Hot water temperature sensor
20
Pressure sensor in the heating circuit
H
Opening in the air/flue pipe
G
N
N
M
M
A
II
O
H
H
C
B
L
J
Q
Q
Q
Q
Q
K
P
D, E
F
I
S
R
T
H.1
Positioning of the opening of a fan-supported flue gas pipe
Installation site
Minimum dimen-
sions
A
Directly below an opening, air bricks, opening windows, etc., that can be opened.
300 mm
B
Above an opening, air bricks, opening windows, etc., that can be opened.
300 mm
C
Horizontally to an opening, air bricks, opening windows, etc., that can be opened.
300 mm
D
Below temperature-sensitive building components, e.g. plastic gutters, down pipes or wastewater
pipes
75 mm
E
Below eaves
200 mm
F
Below balconies or car port roofs
200 mm
G
From vertical wastewater pipes or down pipes
150 mm
H
From external or internal corners
200 mm
I
Above floors, roofs or balconies
300 mm
J
From a surface facing a terminal
600 mm
K
From a terminal facing a terminal
1,200 mm
L
From an opening in the car port (e.g. door, window) which leads into the dwelling
1,200 mm
M
Vertical from a terminal on the same wall
1,500 mm
N
Horizontal from a terminal on the same wall
300 mm
O
From the wall on which the terminal has been installed
0 mm
P
From a vertical structure on the roof
N/A
Q
Above the roof area
300 mm
R
Horizontal from adjacent windows on pitched or flat roofs
600 mm
S
Above adjacent windows on pitched or flat roofs
600 mm
T
Below adjacent windows on pitched or flat roofs
2,000 mm