Analogue Addressable Fire Detector w/ Smart Addressing

TECHNICAL SPECIFICATIONS

ORDER CODE

DESCRIPTION

GLOBAL FIRE EQUIPMENT S.A.

Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL

Tel: 

+351 289 896 560

  •  Sales: 

[email protected]

  •  Technical Support: 

[email protected]

  •  www.

globalfire.pt

Loop Powered - 17 V to 30 V DC

450 uA max.

4 mA - Alarm LED Iluminated

According to EN54-5 or/and EN54-7, EN54-17

0.5-2.5 mm²

20 seconds max.

White / ABS / 95% RH Non-Condensing

0°C to 50°C / -10°C to 85°C

100 mm (D) x 50 mm (H) inc. base / 144 g inc. base

SUPPLY VOLTAGE

CURRENT - QUIESCENT / SURGE

CURRENT - DEVICE IN ALARM

SENSITIVITY

CABLE SIZE

RESET/START-UP TIMES

COLOUR / CASE MATERIAL / MAX. HUMIDITY

NORMAL / TRANSIENT OPER. TEMPERATURE

DIMENSIONS / WEIGHT

ZEOS-AS-S
ZEOS-AS-H
ZEOS-AS-SH
ZEOS-AS-SI
ZEOS-AS-HI
ZEOS-AS-SHI

|  CERTIFICATE  |

ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR WITH SMART ADDRESSING

ANALOGUE ADDR. TEMPERATURE/HEAT DETECTOR WITH SMART ADDRESSING

ANALOGUE ADDR. COMBINED SMOKE & HEAT DETECTOR WITH SMART ADDR.

ANALOGUE ADDR. PHOTOELECTRIC SMOKE DETECTOR W/ ISOLATOR & SMART ADDR.

ANALOGUE ADDR. TEMPERATURE/HEAT DETECTOR W/ ISOLATOR & SMART ADDR.

ANALOGUE ADDR. COMBINED SMOKE & HEAT DETECTOR W/ ISOLATOR & SMART ADDR.

1328-CPR-0526

1328-CPR-0527

1328-CPR-0525

1328-CPR-0609

1328-CPR-0608

1328-CPR-0524

INSTALLATION

MECHANICAL SPECIFICATION

INSTALLING THE BASE

To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat against 
terminals and fastening the wires away from connector terminals. The detector base can be mounted directly onto most standard electrical 
junction boxes.

INSTALLING THE HEAD

Align detector components using provided alignment marks on both the head and base. Align detector mark and short alignment mark on 
base. Fit the detector head onto the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit and 
activate the detection loop. Test the detectors as described below.

TESTING

All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and reconnected at 
the conclusion of testing.

SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector’s smoke chamber for at least 10 seconds. When sufficient 
smoke has entered, the detector will signal an alarm. This will be indicated by the illumination of the 2 Red LEDs provided. Make sure to clear 
smoke out of the chamber before resetting in order to keep the detector at its current sensitivity setting.

HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65°C and 80°C. This requirement can be 
met by some domestic hair dryers. Switch on the warm airflow and check that the temperature is correct and stable. From a distance of several 
cms, direct the airflow at the guard protecting the thermistor. The detector should alarm within 60 seconds. Upon alarm immediately remove 
the heat  source and check that  the Red LEDs of the detector are illuminated. If a detector fails to  activate  within 60 seconds, confirm 
connections and programming. If necessary replace unit. Note: After testing, check that the system is returned to normal operation. Notify 
the appropriate authorities that the testing procedure has been completed and the system is active again.

MAINTENANCE

The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a low 
power vacuum cleaner.   

>> DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR

Detector Head

Detector Base

Alignment Marks

ZEOS-AS

ma_zeosas_01_010001_en_180420

MADE IN PORTUGAL - EU