EXTINGUISHING CYCLE

The extinguishing process can be controlled manually using the buttons available on the front display.

The extinguishing cycle cn be initiated manually executing the following steps:

a) In level 1, silence the internal buzzer using the INTERNAL BUZZER SILENCE button if there are any Fire or 

Fault conditions which have not been acknowledged.

b) If  panel is in access level 1, access level 2 by using either the access key provided or by entering the user 

code 2244.

c)  In  order  to  activate  the  extinguishing  press  the  ACTIVATE  EXTINGUISHING  button.  Activation  is 

confirmed  after  the  internal  buzzer  sounds  for  1  second.  Extinguishing  outputs  will  activated 
inmediately for the duration of the previously programmed extinguihing time. Sounder Circuit 1 will 
also be activated. When the extinguishing cycle is initiated manually, the pre-extinguishing delay is not 
obeyed.

The extinguishing cycle can be stopped once initiated by pressing the ABORT EXTINGUISHING button.

ORDER CODE

TECHNICAL SPECIFICATIONS

CONVENTIONAL MINI-REPEATER PANEL FOR ORION EX - INCLUDES 1 X RS232 INTERFACE

28 V DC nominal derived from Orion Aux. Supply O/P

40 mA

+Supply, -Supply, TX and RX

RS232, RS485, FO or TCP/IP - 1 Display & Control 3 Display Only

95% RH Non-Condensing

-10ºC to 50ºC

1.4 Kg

256 (L) x 194 (W) x 75 (H) mm

White or Red

SUPPLY VOLTAGE

SUPPLY CURRENT

CONNECTIONS

REPEATER NETWORK

MAX. HUMIDITY

OPERATING TEMPERATURE

WEIGHT

DIMENSIONS

COLOUR

ORION EX MINI-REP

Manufacturers of Fire Detection Equipment

globalfire.pt

INSTALLATION MANUAL 1.0 - 06/2015

ORION EX MINI-REP

Содержание ORION EX MINI-REP

Страница 1: ...ufacturers of Fire Detection Equipment globalfire pt INSTALLATION MANUAL 1 0 06 2015 ORION EX MINI REP INSTALLATION MANUAL VERSION 1 0 06 2015 ORION EX MINI REP EXTINGUISHING CONVENTIONAL REPEATER PAN...

Страница 2: ...Panel using 4 different interconnecting technologies RS 232 RS 485 Fiber Optics and TCP IP The unit is provided as standard with an RS 232 interface Power for the ORION EX MINI REP can be supplied fro...

Страница 3: ...ere are no open or shortcircuitsonanyoftheinterconnectingwiresusedforbothsupplyanddatatransmission Allconnectionsshouldbeperformedwithallelementsofthefiredetectionsystemunpowered The Repeater should b...

Страница 4: ...CAL DETAILS 256 mm 246 mm 75 mm 194 mm 187 mm Rear Cable Entry Orion Ex Mini Rep Data Loop Interface PCB Stand offs Orion Ex Mini Rep Back Box Mounting Holes Manufacturers of Fire Detection Equipment...

Страница 5: ...al Hardware and Connections Layout Connect Orion Ex Mini Rep CON3 Data Loop to corresponding interface 24 V DC Ground 0V Earth Manufacturers of Fire Detection Equipment globalfire pt INSTALLATION MANU...

Страница 6: ...lpanel AllotherOrion ExMini Rep s willonlybeabletodisplaysystemstatus Maximum distance between Panel and last Orion Ex Mini Rep shouldbe100meters Connect to cable screens ORION EX MINI REP Interface 2...

Страница 7: ...2 b NOTES On Orion Panel interface JP1 and JP2 should be removed On Orion Ex Mini RepinterfaceJP1andJP2shouldbeON Interface CON3 should be connected to DATA connector Cn3 placed on the undersideofthe...

Страница 8: ...when in Engineering Mode and TESTmodehasbeenselected SUPPLY Multi function indicator used to indicate the presence of supply When in Access Level 1 this LEDispermanentlylit IfinAccessLevel2 enterthis...

Страница 9: ...onlybeoperational attherepeaterafterenteringtheauthorisedusercode Iftheoperation of a switch is only available after succesfully entering the authorised user code it will be clearly stated in this man...

Страница 10: ...r the duration of the previously programmed extinguihing time Sounder Circuit 1 will also be activated When the extinguishing cycle is initiated manually the pre extinguishing delay is not obeyed Thee...

Страница 11: ...ATION MANUAL 1 0 06 2015 ORION EX MINI REP GLOBAL FIRE EQUIPMENT S A S tio dos Barrab s Armaz m Nave Y Caixa Postal 908 Z 8150 016 S o Br s de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalf...

Отзывы: