FAULTS
SUPPLY
This LED will be ON whenever the Main Supply has been removed or has dropped
below 20 Volts.
BATTERY
Indicates that there is low voltage level on the batteries or the battery charger circuit
has failed.
SOUNDERS
If there is a conventional sounder circuit fault, the General Fault LED will be lit and the
Disable Sounders LED in the disablements section will also be lit and flashing.
EARTH
When this indicator is ON there is leakage current flowing from the earth connection/
wiring and any conductor in coming into the panel.
ZONE & INPUT INDICATORS
Individual zone indicators are provided for both FIRE/ALARM and FAULT conditions.
If any of these inputs is disabled then its FAULT LED will also be used to indicate the disablement of that
particular zone/ input. The Zone/ Input disabled LED will be ON along with the Disabled status LED. Flashing
Zone Fault LED along with General fault LED indicates fault on that zone.
CONTROLS -
Some switches will only be operational at the repeater after entering the authorised user code. If the operation
of a switch is only available after succesfully entering the authorised user code it will be clearly stated in this
manual that these functions are only active at access level 2.
NOTE:
If active please SILENCE INTERNAL BUZZER before entering code.
The four switches are numbered to indicate that they are used to enter digits from 1 to 4 for authorised user
code entry.
BUZZER SILENCE ( 1 )
At Access Level 1 this button is used to silence the panel's internal buzzer. Access level 3
used to confirm/accept changes in programming.
RESET ( 2 )
Press this button to reset the panel at access level 2.
LAMP TEST ( 3 )
Press this button at access level 1 or 2 to test all LED indicators and the panel's internal
buzzer. Release when test is finished.
SOUNDERS ( 4 )
Press once to activate/silence sounders. If sounders are active, for example, during a
FIRE condition or in the event of an Evacuation action, pressing this button will stop the
sounders. Auxiliary Relays are not affected by this action.