1-3 Clear Historic Log
7 Monitor Device Counts & Test
Clears the Historic Log.
1-5 Read/Clear Autostart Count
Every time the Panel's power is cycled, the Autostart count is incremented. SYSTEM RESETs from the front
panel button do not increment the Autostart count.
7-1 Device Count, Type & Value
Use this function to check that all loop devices are present.
Use
p
q
to select the device address on that loop.
This function is also useful to confirm the address of the various different types of devices connected to the
Analogue Loop.
Note that in Installation Mode all information is live i.e. the count of devices will change as the panel learns
and device types will be updated if they change. In Active Mode only the device value is live.
7-2 Test Sounders
Use this function to test the audibility of the sounders in a more comfortable manner than pressing SOUND
ALARMS.
The Panel Conventional Sounders will sound for 1 second then be silenced for 9 seconds.
7-3 Sounders on Test Activation
This function allows you to choose an audible confirmation that a device has detected a fire when in test
mode. The audible confirmation consists of a 1 second period of sounder operation. The settings selected by
this function are used by ‘7-4 Test Zones’ and ‘6-4-1 Activate ASET Mode (SAM)’.
ALL SOUNDERS ON DETECTOR TEST activates the Panel Conventional and Loop Sounders.
NOTE:
using this function AFTER ‘7-4 Test Zones’ and ‘6-4-1 Activate ASET Mode (SAM)’ will NOT
change the settings for the zones already in test mode and the loops already in ASET mode.
7-4 Test Zones
Select the Zones you wish to put into test mode.
Exit programming mode, but DO NOT press SYSTEM RESET as this clears all test modes.
In test mode when a detector is activated the LED on the detector will be illuminated and the event will be
reported on the Panel (and Repeaters) for 15 seconds. If selected then the sounders will also operate for 1
second. The LED on the detector is not latched and will clear when the alarm level falls below the alarm
threshold for the device.
Pressing TEST QUEUE REVIEW will report the zones that are in Test Mode.
7-6 Light LED on device
This function can be used to confirm the physical location of a specific detector.
Select the device and SWITCHED ON and press ENTER. The device will typically take a few seconds to
respond.
NOTE:
Reset must be pressed to switch off LEDs.
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4
- FIRE ALARM CONTROL PANEL