1-3 Clear Historic Log  

7 Monitor Device Counts & Test

           

Clears the Historic Log.

1-5 Read/Clear Autostart Count 

Every time the Panel's power is cycled, the Autostart count is incremented. SYSTEM RESETs from the front 
panel button do not increment the Autostart count.

7-1 Device Count, Type & Value     

Use this function to check that all loop devices are present.

Use  

p

q

  to select the device address on that loop.

This function is also useful to confirm the address of the various different types of devices connected to the 
Analogue Loop.

Note that in Installation Mode all information is live i.e. the count of devices will change as the panel learns 
and device types will be updated if they change. In Active Mode only the device value is live.

7-2 Test Sounders                                

Use this function to test the audibility of the sounders in a more comfortable manner than pressing SOUND 
ALARMS.

The Panel Conventional Sounders will sound for 1 second then be silenced for 9 seconds.

7-3 Sounders on Test Activation         

      

This function allows you to choose an audible confirmation that a device has detected a fire when in test 
mode. The audible confirmation consists of a 1 second period of sounder operation. The settings selected by 
this function are used by ‘7-4 Test Zones’ and ‘6-4-1 Activate ASET Mode (SAM)’.

ALL SOUNDERS ON DETECTOR TEST activates the Panel Conventional and Loop Sounders.

NOTE: 

 using this function AFTER ‘7-4 Test Zones’ and ‘6-4-1 Activate ASET Mode (SAM)’ will NOT 

change the settings for the zones already in test mode and the loops already in ASET mode.

7-4 Test Zones                  

Select the Zones you wish to put into test mode.

Exit programming mode, but DO NOT press SYSTEM RESET as this clears all test modes.

In test mode when a detector is activated the LED on the detector will be illuminated and the event will be 
reported on the  Panel (and Repeaters) for 15 seconds. If selected then the sounders will also operate for 1 
second. The LED on the detector is not latched and will clear when the alarm level falls below the alarm 
threshold for the device.

Pressing TEST QUEUE REVIEW will report the zones that are in Test Mode.

7-6 Light LED on device

This function can be used to confirm the physical location of a specific detector.

Select the device and SWITCHED ON and press ENTER. The device will typically take a few seconds to 
respond.

NOTE:

  

Reset must be pressed to switch off LEDs.

  

 

 

Manufacturers of Fire Detection Equipment

globalfire.pt

OPERATING & MAINTENANCE MANUAL - 07/2016

JUNIOR V4

 - FIRE ALARM CONTROL PANEL

Содержание Junior V4

Страница 1: ...ufacturers of Fire Detection Equipment globalfire pt OPERATING MAINTENANCE MANUAL 07 2016 JUNIOR V4 FIRE ALARM CONTROL PANEL OPERATION MAINTENANCE MANUAL VERSION 07 2016 JUNIOR V4 FIRE ALARM CONTROL PANEL ...

Страница 2: ...ealarms 7 1 5 ReadtheFire Fault TestandDisabledqueues 8 1 6 ActiveDelays 9 1 7 LampTest 10 1 8 Performafiredrill 11 1 9 CaretakerTestMode 12 1 10 Disablements 14 1 10 1 Selecteddetectors 14 1 10 2 SoundersDisable 15 1 10 3 AuxiliaryRelays 15 1 10 4 Enable DisableZones 16 1 11 Ifthepaneldisplaysafault 16 1 12 Ifthepaneldisplaysapre alarm 16 2 1 SIMCARD replacement 17 2 2 ReplacingtheElectricalMains...

Страница 3: ...he LED is flashing GREENthenthepanelisinINSTALLATIONmode ZONES ZONES FireZoneindicatorLEDs 1 1 DESCRIPTION OF THE FIRE CONTROL PANEL FASCIA QUEUE REVIEW FAULTS KEYPAD CONTROLS DISABLEMENTS FIRE FAULT PRE ALARM TEST DISABLED SYSTEM ON ALARM FAULT SUPPLY FAULT SYSTEM FAULT DISABLED TEST FAULT FIRE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 FIRE ALARM CONTROL PANEL ENTER ESC DELAYS ACTIVE SELECTED DETECT...

Страница 4: ...tton to confirm the LEDs and LCDdisplayarefunctional SOUNDERS Pressing this button will activate all sounders and panel buzzers main panel and Repeaters Pressing the button again will silence the sounders If the LED is RED it means that the SOUND ALARMS function has been activated by either pressing SOUNDERS ACTIVATE SILENCE switch or during an alarm or Evacuate function is active DISABLEMENTS AUX...

Страница 5: ...ere are ZONES in test mode then pressing this button will show those ZONES on the LCD display If more ZONES are in test mode than can be shown on the LCD display at one time then subsequent presses of the button will step through all the ZONES in test mode If the LED is AMBERit means thatone or more ZONES are in test mode DISABLED If there are disablements then pressing this button will show the d...

Страница 6: ...nal buzzer turn off BUZZER SILENCE LED To stop Sounders press SOUNDER ACTIVATE SILENCE button The LED will also turn off after pressing The STATUS FIRE LED will remain lit RED The STATUS FIRE LED will illuminate RED The fire control panel buzzer will sound continuously The location of the alarm or alarms will be shown on the fire control panel LCD display 1 2 ALARM AuthorizedUserAccess Ifthefireal...

Страница 7: ...NDERS ACTIVATE SILENCE button All sounders turn on The SOUNDERS ACTIVATE SILENCE LED illuminates RED To stop sounders press SOUNDERS ACTIVATE SILENCE button again The SOUNDERS ACTIVATE SILENCE LED extinguishes 1 4 SOUND AND SILENCE THE ALARMS EVACUATION Authorized User Access This section shows you how to turn on and turn off all the sounders in an installation It is identical to a fire drill proc...

Страница 8: ...nceallmessageshavebeendisplayed After20secondsthefirstfireeventwillbere displayed A B C D A B C D FAULT IftheQUEUEREVIEW FAULTLEDisflashingAMBER Press the QUEUE REVIEW FAULT button to display the first queued message Press the button again to review the next queued message Do this until all messages have been reviewed The LED illuminates steady AMBER when all messageshavebeendisplayed After 20 sec...

Страница 9: ...delays are only active when the DELAYS ACTIVE LED is illuminated At all other times the sounders and I O moduleswilloperateimmediatelywhen ifafireisdetected AfterenteringUserAccesscode toenableordisablethesedelayspresstheDELAYSACTIVESbutton Notethatitisalsopossible viatheprogrammingfunctions tosetDELAYSACTIVEtoautomaticallyturnoffatnight Fordetailsontheprogrammablefeaturesanddelaysrefertothe Insta...

Страница 10: ...F EN54 2 EN54 4 CERTIFIED 1328 CPR 0179 STATUS ZONES PressandholdtheLAMPTESTbutton AllLEDsshowninthisdiagramshouldbeilluminated AllpixelsontheLCDdisplayshouldturnblack AllexternalZoneLEDsshouldbeilluminated Release the LAMP TEST button to end the test The LEDs and LCD display will return to their normalcondition 1 7 LAMP TEST General User Access This tests that all LEDs on the fascia are functioni...

Страница 11: ... EN54 4 CERTIFIED 1328 CPR 0179 STATUS ZONES A A 1 8 PERFORM A FIRE DRILL Access Level 2 or Authorized User Access To end the fire drill press the SOUNDERS ACTIVATE SILENCE button The following will occur The sounders stop sounding The SOUNDERS ACTIVATE SILENCE LED extinguishes To start the fire drill press the SOUNDERS ACTIVATE SILENCE button The following will occur All sounders turn on The SOUN...

Страница 12: ...llation Mode When Caretaker Test Mode is entered INITIALIZING may be displayed for up to 20 seconds depending on the system size Caretaker Test Mode is exited by pressing SYSTEM RESET Indication of Caretaker Test Mode The TEST LED will be lit The buzzer will sound for 0 5 seconds every 5 seconds same as FAULT indication ALARM SILENCE will not stop this The message DETECTOR TEST MODE will be displa...

Страница 13: ...Device Detectors and callpoints can only be tested one at a time The LED must be extinguished on the current device before moving on to test the next device Don t use too much smoke spray Disablements All disablements for sounders loop and detectors are ignored during Caretaker Test Mode However the LED on disabled detectors will not be lit when the detector is tested all other aspects of the test...

Страница 14: ...CPR 0179 STATUS ZONES 1 10 DISABLEMENTS Authorized User Access 1 10 1 SELECTED DETECTORS SELECTED DETECTORS When activated The SELECTED DETECTORS LED will be illuminated The STATUS DISABLED LED will be illuminated The QUEUE REVIEW DISABLED LED will be illuminated The disabled detectors can be reviewed using the DISABLED QUEUE REVIEW button Using the programming functions see the Installation Commi...

Страница 15: ... B A D A B C D A B C 1 10 2 SOUNDERS DISABLE To disable the relay and I O module outputs press the AUXILIARY RELAYS button The AUXILIARY RELAYS LED illuminates AMBER The STATUS DISABLED LED illuminates AMBER The QUEUE REVIEW DISABLED LED illuminates AMBER Re press the AUXILIARY RELAYS button to re enable the relays and I O modules 1 10 3 AUXILIARY RELAYS The AUXILIARY RELAYS DISABLEMENT button ena...

Страница 16: ...TER 5 The present status of the zone is shown To change it press ENTER and change the status using the p q arrow keys from enabled to disabled and vice versa When selection is complete press OK Enter ToexitpresstheESCkey EachconsecutivepressoftheESCkeywillrevertbackonestep If any zones are disabled during this time the DISABLED LED in the STATUS area of the panel s fascia will be lit The DISABLED ...

Страница 17: ...e released position push the SIM CARD forward and down until it is almost horizontal with the main panel board Lift the SIM CARD off the connector To install the replacement SIM CARD locate it on the connector almost horizontally with the main panel board push it up and back gently until the retaining clips snap into position Download the panel configuration from the PC if SIM is not pre programme...

Страница 18: ...gcorrectly Notethattousethesefunctionstheinstallerneedstohavegranted UserAccess tothefollowingfunctions By default accessisdenied 1ReviewHistoricLog Allthefunctionsassociatedwithreviewing eventsandsettings 1 1DisplayHistoricLog The panel logs all events in an internal event log It can store a rolling 2000 entries When it is full the latest entryisaddedandtheoldestentrydiscarded Help is automatical...

Страница 19: ...sounder operation The settings selected by thisfunctionareusedby 7 4TestZones and 6 4 1ActivateASETMode SAM ALLSOUNDERSONDETECTORTESTactivatesthePanelConventionalandLoopSounders NOTE using this function AFTER 7 4 Test Zones and 6 4 1 Activate ASET Mode SAM will NOT changethesettingsforthezonesalreadyintestmodeandtheloopsalreadyinASETmode 7 4TestZones Select the Zones you wish to put into test mode...

Страница 20: ...s Levels You have unlimited attempts but if code entry is not started within 10 seconds then the panel will revert back to its default screen While entering the code you are allowed up to 5 seconds between key presses Function Selection The programming functions are arranged using a menu system To select a function or sub menu use either pq and ENTER ESC takes you up a menu level The top level men...

Страница 21: ...d can be photocopied to produce a logbook that conforms to EN54 14 The sample below is for the reference data e g the name of the responsible person whilst the sample onthenextpageisforentryofeventdata REFERENCE DATA Name and address Responsible person Date _________________________ ________________________ Date _________________________ ________________________ Date _________________________ ____...

Страница 22: ...ATE TIME EVENT INITIALS ACTION REQUIRED DATE COMPLETED 2 7 EVENT DATA SHEET Manufacturers of Fire Detection Equipment globalfire pt OPERATING MAINTENANCE MANUAL 07 2016 JUNIOR V4 FIRE ALARM CONTROL PANEL ...

Страница 23: ...ANCE MANUAL 07 2016 JUNIOR V4 FIRE ALARM CONTROL PANEL GLOBAL FIRE EQUIPMENT S A Sítio dos Barrabés Armazém Nave Y Caixa Postal 908 Z 8150 016 São Brás de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Support techs globalfire pt www globalfire pt ...

Отзывы: