www.glendimplex.de 452167.66.02 · FD 9509
EN-4
English
LSA 60TUR
5 Transport
ATTENTION!
When transporting the heat pump, ensure that it is not tilted by more than
45° (in any direction).
A pallet should be used to transport the heat pump to its final in-
stallation location. The basic device can be transported with a lift
truck or a crane.
After the crane transport, the transport eyebolts must be re-
moved and the openings closed with the vent plugs supplied.
After transportation, the transport fastening in the device is to be
removed from both sides of the base.
ATTENTION!
Before commissioning, the transport fastening must be removed.
6 Installation
6.1 General
The device should always be installed on a permanently smooth,
even and horizontal surface. The entire frame should be in direct
contact with the ground in order to ensure an adequate sound-
proof seal, to prevent the water-bearing components from be-
coming too cold and to protect the inside of the device from small
animals. If this is not the case, additional insulation measures
may be necessary. To prevent small animals from entering the
inside of the device, the connection hole in the base plate must
be sealed, for example. Furthermore, the heat pump should be
set up so that the air outlet direction of the fan is perpendicular to
the main wind direction to allow unrestricted defrosting of the
evaporator. The heat pump is designed for installation on even
ground. In the case of different conditions (e.g.: installation on a
platform or flat roof) or there is a greater risk of the heat pump tip-
ping over (due to an exposed position or high wind exposure),
additional protection against tipping over must be provided. The
responsibility for the heat pump installation lies with the specialist
system construction company. During the installation, local re-
quirements such as building regulations, static load of the build-
ing, and wind exposure must be accounted for.
It must be possible to carry out maintenance work without hin-
drance. This is ensured when observing the distances to solid
walls as shown in the figure.
The specified dimensions are valid for stand-alone installation
only.
ATTENTION!
Do not restrict or block the area around the intake or the air outlet area.
ATTENTION!
Observe country-specific building regulations!
ATTENTION!
The physical impacts must be observed for installation close to walls. No
windows or doors should be present in the area surrounding the air outlet
of the fan.
ATTENTION!
In cases of installation close to a wall, there may be more sediment in the
intake and air outlet area due to the air flow. The colder outside air outlet
should discharge in such a way as to not increase the heat losses in
heated neighbouring rooms.
ATTENTION!
Installation in a hollow or in an inner courtyard is not permitted because
cooled air collects at ground level and is drawn in again by the heat pump
during extended periods of operation.