Glen Dimplex 041HOIAOW2 Скачать руководство пользователя страница 20

18

DOK41 HOIAO WxDEN · FD 9912

www.gdts.one

English

Air-to-water heat pump 4 - 6 kW

Step 4: Flanging

Flanging must be carried out as follows with a flanging tool
for R-410A refrigerant as shown in the figure.

Hold the copper pipe steady in a mould with the dimen-
sions shown in the bottom table.

Step 5: Checks

Compare the flanging with the figure on the right.

If the flanging is visibly damaged, cut the relevant section
off and repeat the flanging.

6.7.3 Pipe connections 

The pipe connections on the indoor unit and outdoor unit take
place in two steps. 

Step 1: Initial fastening

Align the centre of the pipe and tighten the screw nuts by
hand.

Step 2: Fastening

Tighten the screw nuts with a spanner.

Torques

6.7.4 Leak test and evacuation

Air and moisture in the cooling system have unwanted effects
as outlined below.
1) The pressure in the system increases.
2) The operating current increases.
3) The cooling (or heating) output falls.
4) Moisture in the cooling circuit can freeze and block the

capillary tubes.

5) Water can cause corrosion on parts in the cooling

system.

This means that the connection pipes must be checked for
leaks and pumped empty to remove any moisture and non-
condensable gases from the system.

Step 1: Preparation

Ensure that every pipe (liquid and intake side) between the in-
door and outdoor unit is connected correctly. Ensure that both
maintenance valves on the liquid and intake of the indoor unit
are closed at this point.

Step 2: Leakage tightness test

Connect a dry nitrogen gas cylinder (with Schrader) on the
maintenance valve.

Apply 40 bar dry nitrogen to the system. Close the cylinder
valve once the test pressure is reached. The next step is to
search for leaks with leak detection spray.

HINWEIS

ºº

º

ºº

º

NOTE

In order to prevent liquid nitrogen from entering the cooling
system, the top side of the gas cylinder must be higher than
the bottom side when pressure is building in the system.

1) All pipe connections (internal and external) must be

checked for leaks with liquid soap. Bubbles indicate a leak.
The soap must then be wiped away with a clean cloth.

2) If no leaks are found on the system, drain off the nitrogen.

External diameter

"A"

mm

mm

10

1.5 ~ 1.7

15.88

1.6 ~ 1.8

External diameter

Torque

mm

Nm

10

34 - 42

12

65 - 81

Rail 

Copper pipe

Clamp

Red arrow marking

Cone

Bracket

Handle

Rail 

"A"

Slanting

The inside shines with no scratches

Smooth all round

The same length 
all round

Damaged 

surface

Cracked

Uneven 

thickness

= Incorrect flanging =

Pipework of 
the indoor system

Screw nut

Pipework

Torque spanners

Pipework of the indoor system

Open-end spanner (fixed)

Connection pipe

Screw nut

Содержание 041HOIAOW2

Страница 1: ...der no DOK41 HOIAO WxDEN EN FD 9912 System M Compact 4 6 kW Installation and Operating Instruction Air to water heat pump in integral design Glen Dimplex Thermal Solutions Dimplex 041HOIAOW2 061HOIAOW...

Страница 2: ......

Страница 3: ...11 6 2 Condensate drain 11 6 3 Connection on heating side 11 6 4 Domestic hot water connection 12 6 5 Temperature sensor connection 13 6 6 Electrical connection 14 6 7 Refrigerant pipe connections 17...

Страница 4: ...2 DOK41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW 16 Information on the use of data 33 17 Declaration of conformity 34...

Страница 5: ...to This unit can be used by children aged 8 and over and by per sons with limited physical sensory or mental aptitude or lack of experience and or knowledge providing they are supervised or have been...

Страница 6: ...s the air i e ex tracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increas ing its pre...

Страница 7: ...alve for generating domestic hot water 9 Switch box with heating controller 10 Overflow valve to guarantee the minimum heating water flow rate to be set by the installer 11 Universal hardware interfac...

Страница 8: ...6 DOK41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW 3 2 Outdoor unit 1 Evaporator 2 Fan 3 Expansion valve 4 Switch box 5 Connection for refrigerant line 1 2 3 4 5...

Страница 9: ...be tilted back by up to 45 and lifted by the handles on the back at the top Tilting over 45 is not permitted without removing the refrigeration circuit beforehand To remove the refrigeration circuit...

Страница 10: ...connection 2 Disconnect the plug connections on the refrigeration cir cuit switch box 3 Loosen the mounting screws 4 Pull the refrigeration circuit out at the side and transport it to the intended loc...

Страница 11: ...5 The responsibility for the heat pump in stallation lies with the specialist system construction company During the installation local requirements such as building reg ulations static load of the bu...

Страница 12: ...ion location at any time of the year The minimum volume of the room where the heat pump is in stalled must be no less than the following value depending on the refrigerant quantity in the device If th...

Страница 13: ...n and shut off option must be im plemented upstream and downstream of the indoor unit Once the heat pump has been connected to the heating sys tem it must be filled purged and pressure tested When doi...

Страница 14: ...re ready for op eration The system must be drained if the heat pump is taken out of service or in the event of a power failure The heating cir cuit should be operated with a suitable frost protection...

Страница 15: ...hat all weather conditions are taken into consideration and the meas ured value is not falsified Mount on the external wall on the north or north west side where possible Do not install in a sheltered...

Страница 16: ...K41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW 6 6 Electrical connection 6 6 1 Circuit diagram Symbol legend see cap 6 6 2 on page 15 Equipment marking see cap 6 6 3 on pag...

Страница 17: ...Hydraulics WPM A210 Master unit A220 Expansion module WPM A300 Electrical distribution system A350 Router A400 Hydraulic installation general A420 Domestic hot water B3 domestic hot water thermostat E...

Страница 18: ...30 V 50 Hz must have a continuous voltage A300 For this reason it should be tapped upstream from the utility blocking contactor or be connected to the household cur rent because otherwise important pr...

Страница 19: ...75 g 225 g HINWEIS NOTE If the indoor unit is mounted 2 5 m or more metres higher or lower than the outdoor unit a cooling technology specialist must perform a separate check to ensure that the devic...

Страница 20: ...the system Step 1 Preparation Ensure that every pipe liquid and intake side between the in door and outdoor unit is connected correctly Ensure that both maintenance valves on the liquid and intake of...

Страница 21: ...ess varies with differ ent lengths of the pipework and the pump output The follow ing table shows the time required for pumping empty Step 4 Filling Once the leakage tightness test and evacuation have...

Страница 22: ...wing procedure to set the over flow valve correctly Close all heating circuits that may also be closed during opera tion depending on how the heat pump is being used so that the most unfavourable oper...

Страница 23: ...by a heating technician Based on current information we recommend using a 5 phosphoric acid solution for cleaning purposes However if cleaning needs to be performed more frequently a 5 formic acid so...

Страница 24: ...from the power supply HINWEIS NOTE Personal protective equipment protective goggles safety shoes and gloves where necessary must be used when work ing on the device Components with plastic parts must...

Страница 25: ...m indoors dB A 33 33 3 7 Air flow Normal operation reduced operation3 m h 3000 2600 3000 2600 4 Dimensions weight and filling quantity 4 1 Device dimensions5 indoors without connections H x W x L mm...

Страница 26: ...ysis of the economic and energy efficiency of the system other parameters in particular the defrosting capacity the bivalence point and regulation should also be taken into consideration These figures...

Страница 27: ...r intake 0 3 m 1 0 m 0 5 m 0 5 m Minimum clearances Direction of air flow 358 40 460 40 17 5 4x Fixing holes base frame for M12 438 540 Hatched area footprint 600 871 500 165 40 40 53 36 676 472 99 16...

Страница 28: ...www gdts one English Air to water heat pump 4 6 kW 12 2 Dimension drawing indoor unit 2 1 2 6 2 8 2 7 2 3 2 4 2 5 2 2 544 600 600 2100 0 40 142 212 282 352 422 573 652 880 63 572 37 ca 0 68 118 195 2...

Страница 29: ...ough refrigerant line 1 6 Optional feedthrough electric wires 1 7 External dimensions wood design variant 1 8 Included pipe set for optional rear connection of the re frigerant lines 2 Indoor unit 2 1...

Страница 30: ...h 0 2 4 6 8 25 20 15 10 5 0 5 10 15 20 25 30 35 40 Air intake temperature in C Coefficient of performance incl proportion of pump output 35 45 55 0 1 2 3 25 20 15 10 5 0 5 10 15 20 25 30 35 40 Air in...

Страница 31: ...47 0 6 m h 0 2 4 6 8 25 20 15 10 5 0 5 10 15 20 25 30 35 40 Air intake temperature in C Coefficient of performance incl proportion of pump output 35 45 55 0 1 2 3 25 20 15 10 5 0 5 10 15 20 25 30 35 4...

Страница 32: ...ons of nitrogen oxides NOx mg kWh Declared load profile L Water heating energy efficiency wh 97 Daily electricity consumption Qelec 5 12 kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is...

Страница 33: ...clared load profile L Water heating energy efficiency wh 89 Daily electricity consumption Qelec 5 51 kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined by measurement nthen...

Страница 34: ...covered by the warranty If it was not possible to remedy the defect the manufacturer shall either deliver a replacement free of charge or issue a reimburse ment for the reduced value In cases in which...

Страница 35: ...t en cryption methods III Use of service providers Personal data required for maintenance purposes such as your address contact details and framework data on the contract is made available to after sa...

Страница 36: ...34 DOK41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW 17 Declaration of conformity You can find and download the current CE conformity declaration at https gdts one m...

Страница 37: ...www gdts one DOK41 HOIAO WxDEN FD 9912 35 Air to water heat pump 4 6 kW English...

Страница 38: ...36 DOK41 HOIAO WxDEN FD 9912 www gdts one English Air to water heat pump 4 6 kW...

Страница 39: ...www gdts one DOK41 HOIAO WxDEN FD 9912 37 Air to water heat pump 4 6 kW English...

Страница 40: ...9 dimplex gdts one www gdts one Gesch ftsstelle sterreich Glen Dimplex Austria GmbH Hauptstra e 71 A 5302 Henndorf am Wallersee T 43 6214 20330 F 43 6214 203304 info dimplex at www dimplex at Office F...

Отзывы: