Hot and Cold water System

Pipe Sizing / Materials

To achieve even distribution of the available supply of hot and cold water, it is 
important in any mains pressure system, that the piping in a dwelling should be 
sized in accordance with BS 6700. This is particularly important in a large property 
with more than one bathroom.

However, the following rule of thumb guide lines should be adequate for most smaller  
property types as long as water pressures are within the recommended range.

1.  A 15mm copper or equivalent external service may be suffi

  cient for a small 1 

bathroom dwelling (depending upon the fl ow rate available), but the minimum 
recommended size for new dwellings is 22mm (25mm MDPE).

2.  The internal cold feed from the main incoming stop tap to the PulsaCoil should 

be run in 22mm pipe. The cold main and hot draw-off  should also be run in 22mm 
as far as the branch to the bath tap.  

3. The 

fi nal branches to the hand basins and sinks should be in 10mm and to the  

baths and showers in 15mm. (1 metre minimum)

4. 

We would recommend that best results for a balanced system are achieved 
by fi tting appropriate fl ow regulators to each hot and cold outlet. This is 
particularly relevant where the water pressures are above the recommended 
water pressure range. Details of suitable fl ow regulators are provided in 
Appendix.

All the recommendations with regard to pipework systems in this manual are generally 
based on the use of BS/EN Standard copper pipework and fi ttings.

However, we are happy that plastic pipework systems can be used in place of copper 
internally as long as the chosen system is recommended for use on domestic hot and 
cold water systems by the manufacturer and is installed fully in accordance with their 
recommendations.

It is also essential that if an alternative pipework material/system is chosen the 
manufacturer confi rms that the design criteria of the new system is at least equivalent 
to the use of BS/EN Standard copper pipework and fi ttings.

Taps/Shower Fittings

Aerated taps are recommended to prevent splashing.

Any type of shower mixing valve can be used as long as both the hot and cold 
supplies are mains fed. However all mains pressure systems are subject to 
dynamic changes particularly when other hot and cold taps/showers are opened 
and closed, which will cause changes in the water temperature at mixed water 
outlets such as showers. For this reason and because these are now no more 
expensive than a manual shower we strongly recommend the use of thermostatic 
showers with this appliance.

The shower head provided must also be suitable for mains pressure supplies.

However, if it is proposed to use a ‘whole body’ or similar shower with a number of 
high fl ow/pressure outlets please discuss with the Gledhill technical department.

The hot water supply to a shower-mixing valve should be fed wherever practical 
directly from the PulsaCoil BP or be the fi rst draw-off  point on the hot circuit. The cold 
supply to a shower-mixing valve should wherever practical be fed directly from the 
rising mains via an independent branch. The shower must incorporate or be fi tted 
with the necessary check valves to provide back-syphonage protection in accordance 
with the Water Regulations.

The supply of hot and cold mains water directly 
to a bidet is permitted provided that it is of the 
over-rim fl ushing type and that a type ‘A’ air 
gap is incorporated.

Hot and Cold Water System

If the length of the hot water draw off  pipework 
is excessive and the delivery time will be more 
than 60 seconds before hot water is available 
at the tap, you may wish to consider using trace 
heating to the hot water pipework such as the 
Raychem HWAT system. Please consult Gledhill 
technical department for further details.

Also a conventional pumped secondary 
circulation system can be used with this 
appliance.

It is important that the cold water pipework 
is adequately separated/protected from any 
heating/hot water pipework to ensure that 
the water remains  cold and of drinking water 
quality.

DESIGN

SYSTEM DETAILS

Содержание PulsaCoil PCBP 120

Страница 1: ... Servicing Instructions Models covered in this manual PulsaCoil PCBP 120 PulsaCoil PCBP 150 PulsaCoil PCBP 180 PulsaCoil PCBP 220 PulsaCoil BP Hot water cylinder utilising off peak electric with an optional solar version ...

Страница 2: ...ill product and we hope you get satisfactory service from Gledhill If not please let us know Benchmarkplacesresponsibilitiesonbothmanufacturersandinstallers Thepurposeisto ensure that customers are provided with the correct equipment for their needs that it is installed commissionedandservicedinaccordancewiththemanufacturersinstructions by competent persons and that it meets the requirements of th...

Страница 3: ...artofthedomesticwaterinstallations The PulsaCoil BP is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the applian...

Страница 4: ...00ppm provision should be made to treat the feed water to water heaters and the hot water circuit of combination boilers to reduce the rate of accumulation of lime scale To comply with this requirement the hardness of the mains water should be checked bytheinstallerandifnecessarytheoptionalfactoryfittedin linescaleinhibitorshould be specified at the time of order for hardness levels between 200 an...

Страница 5: ...roximately 52 C at the bath flow rate of 18 litres min recommended by BS 6700 The temperature is user adjustable Technical Specification Description PCBP 120 PCBP 150 PCBP 180 PCBP 220 Appliance height mm 1131 1332 1533 1734 Appliance width mm 560 560 560 560 Appliance depth mm 605 605 605 605 Appliance weight empty kg 54 63 69 78 Approx weight full kg 172 205 234 268 Total volume nominal litres 1...

Страница 6: ...pupcistern not shown Note Both immersion heaters are low watts density type with incaloy 825 sheaths and are specially manufactured to suit Thermal Stores It is recommended that any replacements should be obtained from Gledhill Building Products Optional Extra Equipment In line scale inhibitor for mains water services with hardness levels between 200 and 300ppm mg l fitted but ready for wiring by ...

Страница 7: ...D Width E Depth F PCBP 120 1881 600 620 PCBP 150 2082 600 620 PCBP 180 2283 600 620 PCBP 220 2484 600 620 Note The Appliance dimensions above do not allow for the100mm high installation base The following table of minimum cupboard dimensions only allow the minimum space requiredfortheappliance includingthetopup cistern Any extra space required for shelving etc in the case of airing cupboards etc m...

Страница 8: ...ified If a warning overflow pipe is NOT provided the F E Cistern should be filled from a temporary hose connection incorporating a double check valve This can be from a temporary hose connection supplied from a cold water tap or a permanent cold branch provided adjacent to theTop up Cistern The temporary connection must be removed once the appliance is filled Note All dimensions are shown in mm an...

Страница 9: ...ptionalpolyphosphate type inhibitor should be specified at the time of order However this will need to be fitted by the installer at a suitable point in the cold water supply to the appliance The hot water flow rate from the PulsaCoil BP is directly related to the adequacy of the cold water supply to the dwelling This must be capable of providing for those services which could be required to be su...

Страница 10: ...o the use of BS EN Standard copper pipework and fittings Taps Shower Fittings Aerated taps are recommended to prevent splashing Any type of shower mixing valve can be used as long as both the hot and cold supplies are mains fed However all mains pressure systems are subject to dynamicchangesparticularlywhenotherhotandcoldtaps showersareopened and closed which will cause changes in the water temper...

Страница 11: ...ost facility is reduced if a better off peak tariff can be agreed with the electrical supply company see Model Selection Guide on page 5 The typical wiring arrangement is shown in figure 1 7 An economy 7 controller eg Horstman Electronic 7 is used for a manual boost and automatic off peak heating of hot water If a factory fitted scale inhibitor has been specified thenitshouldbewiredtoapermanent su...

Страница 12: ... its design temperature Cupboardtemperatureswillnormallybeslightlyhigherthaninaconventionalsystem and the design of the cupboard and door will need to take this into account No ventilation is normally required to the cupboard The separate Top up cistern will need to be located on top of the appliance or at high level in the cupboard housing the PulsaCoil BP The dimensions and clearances are provid...

Страница 13: ... for slings lifting beams etc Beforeinstallationthesiterequirementsshould be checked and confirmed as acceptable The plastic cover and protective wrapping shouldberemovedfromtheapplianceand the installation base provided placed in position Theappliancecanthenbeliftedintopositionin the cupboard on top of the base and the front panelremovedbyunscrewingthe2screwsand liftingthedoorupandout readyforcon...

Страница 14: ...open vent B 15mm Cold feed expansion C 22mm Incoming mains cold water D 22mm Domestic hot water E Drain tap connection Note The safety open vent and cold feed expansion must be connected to the top up cistern using the pipework assembly provided Do not alter or connect any pressure relief device to the vent pipe of this water heater All factory made joints should be checked after installation in c...

Страница 15: ...as supplied should be used to connect to the top up cistern and pipework site run by the installler to connect this to the appliance Obviously any pipework in the roof space and the feed and expansion cistern will need to be adequately insulated to protect against frost damage Combined feed and open pipe arrangements must not be used No valves should be fitted in the safety open vent which must be...

Страница 16: ...abel if it is a manual fill model If the optional level gauge has been provided the level will be shown by the red float Ifaballvalveisprovided turndowntheservicingvalveoncethesystemisfinally filled to the point where the warning overflow pipe will cope with the discharge arising from a ballvalve failure If an overflow is not provided ensure the temporary filling hose is isolated and removed from ...

Страница 17: ...3 bar 2 DO check the flow rate of the incoming cold water main is adequate to meet the maximum hot and cold water simultaneous demands 3 DO check that all connections are in accordance with the labelling on the thermal store 4 DO NOT switch on the immersion heaters until you have checked that the appliance is full of water ie there is water in the top up cistern 5 DO check the water level is corre...

Страница 18: ...with dual control safety thermostat XB482 2 Bottom immersion heater Incalloy 825 immersion heater with dual control safety thermostat XB482 3 Brawa mix thermostatic hot water blending valve XC007 4 Scale inhibitor PCB XB142 5 11 Safety Rod Stat XB114 4 3 1 2 SERVICING SHORT PARTS LIST ...

Страница 19: ...Stourbridge West Midlands DY8 1PA TELEPHONE 01384 442611 FAX 01384 442612 Water Savings Water Related Costs Can Be Reduced By Good Plumbing Practice TAPS MIXERS SHOWERS Unregulated 25 30 l m Regulated 10 12 l m Over 20 l m 5 6 or 8 l m 2 tap half open Fitted with regulator Unregulated 4 Fixing Options For Taps Mixers 1 MK Range Combined Regulators Aerator forscrewingontoTaps Mixerswithinternal ore...

Страница 20: ...Page 20 APPENDIX APPENDIX B ...

Страница 21: ...two persons to have a purposely designed hold at the top of the appliance to ensure easy lifting at the top of the product e Taking the lead for team lifts As more than one person is required for these products ensure that one person is taking the lead This may be you so ensure that each person that is helping is made aware of the weight and of the items listed within this assessment Make sure you...

Страница 22: ...Page 22 NOTES ...

Страница 23: ...Page 23 NOTES ...

Страница 24: ...on chloride sulphate Max 300 mg l in total 9 2 5 Whereappropriatetheunithasbeenregularlymaintainedasdetailedintheinstallationandserviceinstructions 9 2 6 Defects caused by corrosion or scale deposits are not covered by any Guarantee 9 2 7 Where we agree to rectify any defect we reserve the right to undertake the work on our own premises 9 2 8 We will not accept any labour charges associated with r...

Страница 25: ... i the Purchaser shall hold the goods in a fiduciary capacity for us and shall store the same separately from any other goods in the Purchaser s possession and in a manner which enables them to be identified as our goods ii the Purchaser shall immediately return the goods to us should our authorised representative so request All the necessary incidents associated with a fiduciary relationship shal...

Страница 26: ...Other Is the cylinder solar or other renewable compatible Yes No What is the hot water temperature at the nearest outlet C All appropriate pipes have been insulated up to 1 metre or the point where they become concealed Yes UNVENTED SYSTEMS ONLY KHUH LV WKH SUHVVXUH UHGXFLQJ YDOYH VLWXDWHG LI WWHG What is the pressure reducing valve setting bar DV D FRPELQHG WHPSHUDWXUH DQG SUHVVXUH UHOLHI YDOYH D...

Страница 27: ...ame Telephone No Comments Signature SERVICE 05 Date Engineer name Company name Telephone No Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Comments Signature SERVICE 09 Date Engineer name Company name Telephone No Comments Signature SERVICE 02 Date Engineer name Company name Telephone No Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Comments...

Страница 28: ...mer support with a range of services including Low cost annual repair and maintenance contracts direct from Gledhill Annual servicing and safety checks Expert response to out of warranty breakdowns at fixed charges Please call 08445 679898 or visit www gledhill net for further details Only the best is acceptable FM 02057 To protect our environment we use copper a totally recyclable metal which nev...

Отзывы: