This series of products include two control systems, based on which different adjustment methods apply. Please select the 

proper adjustment method according to the type of control system with the storage box you purchased.

6. Operating Instructions

a. Door switch indicator
When the door is opened, the door switch indicator is on; When the door is closed, the door switch indicator is off.
b

.

Defrosting indicator

When the refrigerator enters the defrosting state, the defrosting indicator is always on; When the refrigerator exits the 

defrosting state, the defrosting indicator is always off.

c. Key lock indicator

When the keys are in lock state, none of the keys respond, and the key lock lights up. In this case, after pressing the 

up key+down key for 3s, you will be prompted to enter the password, which is defaulted as "005." After entering it 

correctly, press the Set/Mute Multiplex key, and the key lock will be released. At this time, the key lock indicator will 

be off. In the unlock state, if no key is pressed for 60s, the key lock is started, and the key lock indicator is on. Long 

press the up key + down key for 3s, and the keys are locked.

d

.

Power-off indicator

The refrigerator is normally powered by 220V. When the input power is turned off, the buzzer will be triggered, the 

digital tube flashes the power-off code "PF" alternately at 3s intervals, and the power-off indicator is on. When the input 

power is turned on, it returns to normal, and the power-off indicator is off.

e

.

Print indicator

When the printer is not working, the indicator is off; When the printer is working, the indicator is on.
f

.

Door heating indicator

When the door heating is turned off, the door heating indicator is off; When the door heating is turned on, the door 

heating indicator is on.

g

.

Refrigeration indicator

If the compressor is in working condition, the refrigeration indicator is on; If the compressor is in a shutdown state, 

the cooling indicator is off.

h

.

Mute indicator

When the alarm tone key is muted, the indicator is on; When the alarm mute function is canceled, the indicator is 

off.

i

.

Low battery level indicator

When the battery voltage is less than 8V, the buzzer will be triggered, the low battery indicator will be on, and the 

digital tube will flash the low battery code "BL" alternately at intervals of 3s; When the battery voltage is greater than 

12V, the buzzer will be turned off, the low battery indicator will be off, and the digital tube will resume normal display.

j

.

Serial port indicator

When the reserved RS-485 serial port is not connected to the equipment, the serial port indicator will be off; When 

the equipment is successfully connected to the reserved RS-485 serial port, the serial port indicator will be on.

k.Fan indicator
When the evaporator fan is turned on, the fan indicator is on; when the evaporator fan is turned off, the fan indicator 

is off.

1) Description of display icon indicator 

    (as shown in the right diagram)

2

)

temperature display window, which displays the average temperature inside the cabinet in °C under

normal operation;

View ambient temperature:
In the key lock state, press

key, and digital tube displays the ambient temperature, and returns to normal 

display after 5 s without key operation, or pressing

and

 

 

.

 

In the key unlock state, press

key, and digital 

tube displays ambient temperature, and returns to normal display after 5s without key operation.

Humidity check: key unlocked state, long press

and

 

 

, digital tube display humidity, no press any Key 

operation after 5 seconds or press

and 

 

, return to normal display.

3

)

is the set/mute key; In case of no alarm state and key unlock state, press 

 

, and display the ambient

temperature for 5s and then return to normal display; In the unlock state, press

 

 

 

for more than 3s, and enter the

user menu.

When buzzer is triggered (including cabinet high temperature alarm, door opening alarm, sensor failure alarm, etc.)

and in the key unlock state, press

 

 

 

for the first time, and the buzzer stops ringing, and the ambient temperature

is displayed for 5s, after which the normal display is resumed (pressing the mute button is only to turn off the buzzer
for alarming this abnormal state, for example troubleshooting, and the buzzer will be triggered next time for any
abnormality). Then press

 

 

 

again, trigger the buzzer, display the ambient temperature for 5s, and resume the

display of chamber temperature and alarm state. In the key unlock state,

 

 

 

can be used as a setting key.

In unlock state and parameter setting mode, press this key to display parameter values and parameter names. If the

pressing time is longer than 3 seconds, save the settings and return to the normal interface.

4

)

is a up key; In parameter setting mode, move to the next parameter or increase the parameter value. For

example, when setting the set temperature, increase the set temperature value. When setting the parameter value,
long press the up button, and the parameter will increase rapidly. Under normal conditions, long press the up key for
3 seconds to import the data of the USB flash drive in 12 months.

5

)

is a down key;

In parameter setting mode, move to the previous parameter or decrease the parameter value.
For example, when setting the set temperature, reduce the set temperature.
When setting the parameter value, long press the down button, and the parameter will decrease rapidly.
6

)

is a print key;

The system can keep 7 days of data for printing, and press the print key to print the temperature within the set time

period.

7

)

is a light switch key;

When the equipment is powered on, the lights are turned off by default. Press the light switch key to turn the lights

on and off. When the light is off, it can be turned on when the door is opened and turned off when the door is
closed; When the light is off, it does not change when the door is opened or closed. This equipment has two
functions: automatic lighting and manual lighting. In the automatic lighting state, the lighting lamp will be on
immediately when the door is opened, and the lighting lamp will be off after a 5 seconds delay; The user can also
turn on the lighting lamp manually. In this case, the lighting lamp is always on (the indicator light above the key is
on) without being controlled by the door opening and closing. Only when the manual lighting is turned off by
pressing the light switch key again can the lighting lamp be automatically on (the indicator light above the key is off).

8

)

USB data export;

Automatic export: When the USB interface is connected to the USB flash drive, the buzzer of the recorder beeps

once, displaying "on," and PDF files of the data of the current month and the previous month are generated in the
USB flash drive. After the data transmission is completed, the buzzer beeps once, displaying "End," and the normal
display resumes after 6s.

Note: When there is less data, the digital tube will not display "on" and "End."

Manual export: In the key unlock state, and when the USB flash drive is connected and the file is not being

generated, press the key up for 3 seconds, and the digital tube will display "d01." Press the up key or down key to
adjust "d00~d12," and press

 

 

 

key to obtain the file generation (d00) or generate the PDF file of the record data

of the previous months (1-12).

1. Function description of Type A control panel (Applicable to YC-55L, YC-55EL, YC-75L, YC-75EL, YC-315L, YC-395L, 

YC-395EL, YC-400L, YC-525L, YC-725L, YC-1015L, YC-1015EL, YC-1505L)

10

11

6.1 Function Introduction

Type A control panel

Printer (optional)

Door 

switch

Power 

failure

Mute

WIFI

Print

Electric 

quantity

Defrosting

Door 

heating

Serial 

port

Key lock

Refrigeration

Fan

Содержание GL-RG-12M

Страница 1: ...GL RG 4M GL RG 12M GL RG 16M GL RG 23M OPERATION MANUAL Applicable product model www aegisfridge com ...

Страница 2: ...roduct composition and overview 6 Operating Instructions 6 1 Function Introduction 6 2 Optional function 7 Maintenance and Service 7 1 Equipment Maintenance 7 2 Equipment Discontinuation 7 3 Maintenance Replacement and Recovery of Rechargeable Batteries 8 Troubleshooting and Maintenance Services 9 Specifications 10 Packing List 11 Electrical Schematic Diagram 1 2 4 4 4 4 5 5 6 7 10 10 19 19 20 19 ...

Страница 3: ...er products For your safe and convenient use and reasonable maintenance of the equipment please read the Operation Instructions carefully before use and keep it properly for reference The equipment operator can copy some chapters of this operation manual but only for internal use for example to instruct the user how to deal with emergencies These chapters are clearly marked in the catalog of the m...

Страница 4: ...utlet tightly to ensure firmness and reliability so as to avoid electric leakage After installation the power plug must be within reach so that the power plug can be unplugged in time in case of emergency Separate special outlets must be used and grounded reliably The cross sectional area of the copper 2 conductor in the wall connected with the outlet must be more than 4mm Do not lengthen the powe...

Страница 5: ...r any outlet of the equipment otherwise electric shock or injury may be caused due to accidental contact between the above objects and moving parts In order to ensure the normal operation and ventilation and heat dissipation of the equipment the back left and right sides of the cabinet shall be at least 30cm away from the wall and the air inlet and air outlet must not be blocked by obstacles This ...

Страница 6: ... cold and heat sources and strong electromagnetic interference which will affect the normal operation of the control system and directly damage the system in severe cases 4 2 Installation Site Figure N and E ends cannot be connected In order to operate the equipment normally and obtain the best performance level the installation site of the equipment shall meet the following requirements ò It cann...

Страница 7: ...rt both ends of the handle cover into the corresponding grooves of the handle seat and then press it to close it 4 3 Preparation before use 4 4 First Power on When using the equipment for the first time please follow these steps 1 After the equipment is placed leveled and cleaned it shall stand for more than 24 hours and then power it on to ensure the normal operation of the equipment 2 Under no l...

Страница 8: ...reached Electrical appliances without production license shall not be used inside the equipment Do not change the set temperature frequently in a short time otherwise the expected setting effect may not be achieved due to the large temperature inertia Ensure that there is a certain air circulation space around the cabinet when putting in items especially do not block the temperature sensor in the ...

Страница 9: ...M Figure II GL RG 4M USB interface Door body Display panel Door lock Test hole Cabinet Caster Adjust feet Power switch Remote alarm interface Rs485 interface Door lock Test hole Door handle Cabinet Adjust feet Caster Door body USB interface Display panel ...

Страница 10: ...8 Figure III Figure IV Caster Door handle Door body Cabinet Caster Door lock Adjust feet Steel wire shelf Test hole Printer optional Display panel power switch on the back USB interface ...

Страница 11: ...he product consists of cabinet door glass door structure or foam door structure refrigeration system and control system Scope of application It is suitable for storing items in hospitals pharmacies epidemic prevention stations research institutions biopharmaceuticals and other units Figure V Steel wire shelf Door body Caster Cabinet Test hole Printer optional Display panel power switch on the back...

Страница 12: ...ff When the printer is working the indicator is on f Door heating indicator When the door heating is turned off the door heating indicator is off When the door heating is turned on the door heating indicator is on g Refrigeration indicator If the compressor is in working condition the refrigeration indicator is on If the compressor is in a shutdown state the cooling indicator is off h Mute indicat...

Страница 13: ...y for 3 seconds to import the data of the USB flash drive in 12 months 5 is a down key In parameter setting mode move to the previous parameter or decrease the parameter value For example when setting the set temperature reduce the set temperature When setting the parameter value long press the down button and the parameter will decrease rapidly 6 is a print key The system can keep 7 days of data f...

Страница 14: ...0 5 0 Temperature setting 2 H 0 0 10 0 5 0 Set value of high temperature alarm set H When H 0 High temp alarm is disabled When the alarm is over high temp alarm set H1 will be displayed on the controller 3 L 0 0 10 0 4 0 Set value of low temperature alarm set L When L 0 Low temp alarm is disabled When the alarm is below low temp alarm set L1 will be displayed on the controller 4 Pt 0 240 min 20 Pr...

Страница 15: ...arm L1 Low temperature alarm H2 Alarm for high ambient temperature H3 Condenser overheat alarm do Door opening alarm PF Power failure alarm bL Battery low alarm Er The recorder is not connected LoF Battery low alarm EE Communication failure 5 Alarm display ...

Страница 16: ...t above the key is off e PRINT optional The system can keep 7 days of data for printing Press the print key to print the temperature within the set time period f In parameter setting mode reduce the parameter value For example when setting the set temperature reduce the set temperature When setting the parameter value long press the down button and the parameter will decrease rapidly g In paramete...

Страница 17: ...d displays LoF the recorder is not started Meanwhile press and key for 3s and LoF disappears the recorder is started 2 Function setting of Type B control panel 1 Power on and turn on the power switch on the back of the cabinet and the equipment will enter the working state 2 User parameter settings Unlock In normal operation state simultaneously press and key for 3s and the digital tube displays t...

Страница 18: ...is opened and closed again during the heating period the heating time will be updated again Mode 2 When the compressor runs Heater is on When the compressor stops the heater Will automatically off after one min Mode 3 When the humidity in the cabinet is more than 80 the door heating is on and when the humidity in the cabinet is moderately less than 60 the door heating is off Mode 4 Door heating is...

Страница 19: ...ting paper has been installed at the factory When the paper is used up after a long time you may purchase the same paper for installation The installation steps are as follows Click the cylindrical button on the printer to open the cover of the printer Put the printing paper into the printer box and pull the paper head of the roll so that the paper slightly exposes from the upper port of the box c...

Страница 20: ...and RS485 interface The remote alarm terminal is installed on the back of the cabinet and the alarm signal is output by the terminal The load bearing capacity of the terminal is 30V 2A DC Users can choose normally open normally closed and common terminals according to their own needs 18 RS 485 ...

Страница 21: ...month and the power lock switch should be turned on so that the equipment can run for a period of time to complete charging and each charging time should be no less than 24 hours When the working power supply is interrupted the power lock switch of the equipment shall be turned off in time otherwise it will cause power loss in battery and even permanent damage to the battery in severe cases The ma...

Страница 22: ...roduct may fail Please observe the operation of equipment in time during use If there is any abnormality please check and handle it according to the following table first If the abnormality can t be changed please inform our service center in time and we will serve you wholeheartedly to avoid losses Fan motor replacement time about 6 years Service life of the product 10 years Notes 20 After the eq...

Страница 23: ...540X764 YC 130L 16 32 C N R134a 110g 220 230V 50 2 8 C 130 155 51 625X650X810 YC 315L 16 32 C N R600a 22g 220 230V 50 2 8 C 315 285 87 673X650X1762 YC 395L 16 32 C N R600a 25g 220 230V 50 2 8 C 395 290 95 673X650X1992 YC 395EL 16 32 C N R600a 25g 220 230V 50 2 8 C 395 250 89 673X650X1992 YC 400L 16 32 C N R290 65g 220 230V 50 2 8 C 400 500 116 645X700X2016 YC 525L 16 32 C N R290 75g 220 230V 50 2 ...

Страница 24: ...mity Accessory package Key The door handle accessory applies to models YC 725L YC 1015L YC 1015EL and YC 1505L Keys apply to models YC 55L YC 55EL YC 75L YC 75EL YC 130L YC 315L YC 395L YC 395EL YC 400L YC 525L YC 725L and YC 1505L The specific packing list shall be subject to the physical objects received 1 1 1 2 Operation Manual ...

Страница 25: ...EL YC 400L YC 525L YC 725L YC 1015L YC 1015EL YC 1505L Applicable to YC 130L The technical data and electrical schematic diagram shall be subject to the nameplate on the product and the electrical schematic diagram in case of any improvement of the product design We sincerely apologize for any inconvenience that might be caused ...

Отзывы: