Installation
37
Cod. 598250
Rev. 09/0918
Circuit breaker.
Install an earth-leakage protected circuit breaker.
Characteristics:
installed in an easily accessible place.
number of poles and intensity: consult ELECTRICAL CONNECTION table (section 1.6)
A type.
protected against pulse currents, harmonics, the presence of continuous components, etc. (consult
manufacturer specifications)
Safety switch.
Install an Automatic on/off Switch, outside the washer, with individual protection for each
machine.
Characteristics:
number of poles and intensity: consult ELECTRICAL CONNECTION table (section 1.6)
C type with top opening at 3 mm (0.12 in)
must isolate electrical source phases and the N cable
mechanically lockable
installed in an easily accessible place.
CAUTION!
On machines with ETL mark, the SAFETY SWITCH must be UL489 approved
.
3.3.3. Machine electrical connection
FOR A CORRECT CONNECTION, FOLLOW THE INDICATIONS OF THE SECTIONS BELOW
RMS610, REM025 Models
Disconnect and mechanically lock the external
automatic switch.
Open the machine’s terminal box.
Fix the electrical supply hose to the stuffing box at
the washer entry.
Connect the wires to the connection board.
The connection sequence of the cables to the
entry board varies according to the number of
phases and the voltage of the washer. On the
label posted next to the entry board are indicated
the different connection options. Refer to Fig. 3.7.
Fig. 3.7