Power supply 160 mA, 320 mA, 640 mA, 1280 mA with integrated choke

Operation with emergency power systems

The power supply can be used in combination with centrally supplied emergency power sys-
tems. In this way, the function of the KNX system and the control of the most important func-
tions can be ensured in emergency operation.

Statutory and standard specifications for emergency power and emergency lighting sys-
tems vary from country to country. In any event, the user / technical planner must check
whether the specific specifications are observed.

Cable lengths

For KNX line segments and power supplies the following rules apply:

Bus line length per lin segment: Max. 1000 m

Bus line length between power supply and KNX bus subscriber: Max. 350 m

Bus line length between two KNX bus subscribers: Max. 700 m

6

Technical data

Rated voltage

AC 220 ... 240 V~

The device is operable in the range of 180 V
AC … 264 V AC.
Mains frequency

50 / 60 Hz

Power loss (max. load on all outputs)
Art. no. 2120 00

max. 1.5 W

Art. no. 2122 00

max. 1.8 W

Art. no. 2130 00

max. 2.9 W

Art. no. 2138 00

max. 6.4 W

Efficiency
Art. no. 2120 00

approx. 76%

Art. no. 2122 00

approx. 84%

Art. no. 2130 00

approx. 87%

Art. no. 2138 00

approx. 86%

Rated voltage DC

DC 240...250 V

KNX
KNX medium

TP256

Bus output voltage

DC 28 ... 31 V SELV

Output current
Art. no. 2120 00

160 mA (all outputs)

Art. no. 2122 00

320 mA (all outputs)

Art. no. 2130 00

640 mA (all outputs)

Art. no. 2138 00

1280 mA (all outputs)

Short-circuit current
Art. no. 2120 00

max. 1 A

Art. no. 2122 00

max. 1 A

Art. no. 2130 00

max. 1.5 A

Art. no. 2138 00

max. 3 A

Connection type for bus

device connection terminal

Parallel operation with identical power supply
Art. no. 2120 00

Yes

Art. no. 2122 00

Yes

7 / 8

82597322

06.05.2019

Содержание 2120 00

Страница 1: ...Operating instructions 1 Safety instructions Electrical devices may only be mounted and connected by electrically skilled persons Serious injuries fire or property damage possible Please read and foll...

Страница 2: ...NX bus line for 20 seconds Press between 2 4 seconds Permanently switch off the KNX bus line Press longer than 4 seconds Terminate the permanent reset Press the button 9 Signal contact for diagnostic...

Страница 3: ...n off off flashes 2 5 Hz closed Permanent re set on off off flashes 0 25 Hz closed Overvoltage flashes 0 5 Hz off on until the message is acknow ledged off open until the message is acknow ledged Over...

Страница 4: ...ain and the LED Reset switches off 5 Information for electrically skilled persons DANGER Mortal danger of electric shock Disconnect the device Cover up live parts 5 1 Fitting and electrical connection...

Страница 5: ...azardous voltages in the connec tion area The total load of the outputs can be subdivided as desired Do not exceed the total rated current Do not connect any other products to the bus output This migh...

Страница 6: ...g to the connection example Figure 5 L N L N PE max 2 A Figure 5 Application example signal lamp for optical operating display Connect the KNX binary input according to the connection example Figure 6...

Страница 7: ...s line length between two KNX bus subscribers Max 700 m 6 Technical data Rated voltage AC 220 240 V The device is operable in the range of 180 V AC 264 V AC Mains frequency 50 60 Hz Power loss max loa...

Страница 8: ...nnection mode device connection terminal Finely stranded with conductor sleeve 0 5 2 5 mm 7 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade Please...

Отзывы: