Power supply 160 mA, 320 mA, 640 mA, 1280 mA with integrated choke

Figure 2: 1280 mA power supply – view

(1)

Connection of mains

(2)

LED Betrieb, green
On: Normal operation
Flashes: Overload or overvoltage
Off: No mains voltage or internal error

(3)

LED Überlast, red
On: Overload or short-circuit on KNX bus line or output DC 30 V

(4)

LED Überspannung, yellow
On: Overvoltage on KNX bus line or output DC 30 V

(5)

Output DC 30 V

(6)

Output Bus for KNX bus line

(7)

LED Reset, red
Flashes rapidly 2.5 Hz: Reset for 20 seconds
Flashes slowly 0.25 Hz: Permanent reset

(8)

Button Reset
Acknowledge the diagnostic message: Press briefly, < 0.5 seconds
Switch off the KNX bus line for 20 seconds: Press between 2...4 seconds
Permanently switch off the KNX bus line: Press longer than 4 seconds
Terminate the permanent reset: Press the button

(9)

Signal contact for diagnostic message
Closed: Normal operation
Open: After overload, overvoltage or in case of a power failure

3

 Function

System information

This device is a product of the KNX system and complies with the KNX directives. Detailed tech-
nical knowledge obtained in KNX training courses is a prerequisite to proper understanding.

Intended use

Supplying KNX devices with bus voltage

Supplying devices with direct current

Mounting on DIN rail according to EN 60715 in sub-distribution unit

Product characteristics

Output with integrated inductance for supplying KNX bus lines

DC 30 V output for supplying additional devices

2 / 8

82597322

06.05.2019

Содержание 2120 00

Страница 1: ...Operating instructions 1 Safety instructions Electrical devices may only be mounted and connected by electrically skilled persons Serious injuries fire or property damage possible Please read and foll...

Страница 2: ...NX bus line for 20 seconds Press between 2 4 seconds Permanently switch off the KNX bus line Press longer than 4 seconds Terminate the permanent reset Press the button 9 Signal contact for diagnostic...

Страница 3: ...n off off flashes 2 5 Hz closed Permanent re set on off off flashes 0 25 Hz closed Overvoltage flashes 0 5 Hz off on until the message is acknow ledged off open until the message is acknow ledged Over...

Страница 4: ...ain and the LED Reset switches off 5 Information for electrically skilled persons DANGER Mortal danger of electric shock Disconnect the device Cover up live parts 5 1 Fitting and electrical connection...

Страница 5: ...azardous voltages in the connec tion area The total load of the outputs can be subdivided as desired Do not exceed the total rated current Do not connect any other products to the bus output This migh...

Страница 6: ...g to the connection example Figure 5 L N L N PE max 2 A Figure 5 Application example signal lamp for optical operating display Connect the KNX binary input according to the connection example Figure 6...

Страница 7: ...s line length between two KNX bus subscribers Max 700 m 6 Technical data Rated voltage AC 220 240 V The device is operable in the range of 180 V AC 264 V AC Mains frequency 50 60 Hz Power loss max loa...

Страница 8: ...nnection mode device connection terminal Finely stranded with conductor sleeve 0 5 2 5 mm 7 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade Please...

Отзывы: