Power supply 160 mA, 320 mA, 640 mA, 1280 mA with integrated choke

Nominal current can be subdivided to outputs as desired

Reset button

Short-circuit proof

Overvoltage proof

No-load proof

Suitable for operation in systems with emergency power supply

Potential-free signal contact for operating and diagnostic message

Two identical power supplies can be connected in parallel (with the versions 160 mA, 320
mA and 640 mA)

4

Operation

Acknowledging the diagnostic message

After detecting a overvoltage or a short circuit the LED and the signal contact signal the event
until the message is acknowledged.

Press the Reset button for less than 0.5 seconds.

LED functions and signal contact

LED 
Betrieb (2),
green

LED 
Überlast (3),
red

LED 
Überspan-
nung (4), yel-
low

LED 
Reset (7), red

Signal contact
(9)

Normal opera-
tion

on

off

off

off

closed

Reset for
20 seconds

on

off

off

flashes 2.5 Hz closed

Permanent re-
set

on

off

off

flashes
0.25 Hz

closed

Overvoltage

flashes 0.5 Hz off

on (until the
message is
acknow-
ledged)

off

open (until the
message is
acknow-
ledged)

Overload,
short-circuit

flashes 0.5 Hz on (until the

message is
acknow-
ledged)

off

off

open (until the
message is
acknow-
ledged)

Voltage
failed / internal
error

off

off

off

off

open

In normal operation the control of the power supply is not necessary. The button (8) is recessed
and thus prevents that it is inadvertently actuated in operation.

Reset function and Reset button

When resetting a bus segment, the output voltage of the power supply is switched off. At the
same time the bus line is short-circuited so that all connected bus devices are disconnected
from the bus voltage.

Resetting the bus line for 20 seconds

Press the Reset button (8) between 2 ... 4 seconds.
The bus line is short-circuited for 20 seconds.

The LED Reset (7) flashes quickly.

After 20 seconds the bus voltage is switched on again and the LED Reset  switches off.

3 / 8

82597322

06.05.2019

Содержание 2120 00

Страница 1: ...Operating instructions 1 Safety instructions Electrical devices may only be mounted and connected by electrically skilled persons Serious injuries fire or property damage possible Please read and foll...

Страница 2: ...NX bus line for 20 seconds Press between 2 4 seconds Permanently switch off the KNX bus line Press longer than 4 seconds Terminate the permanent reset Press the button 9 Signal contact for diagnostic...

Страница 3: ...n off off flashes 2 5 Hz closed Permanent re set on off off flashes 0 25 Hz closed Overvoltage flashes 0 5 Hz off on until the message is acknow ledged off open until the message is acknow ledged Over...

Страница 4: ...ain and the LED Reset switches off 5 Information for electrically skilled persons DANGER Mortal danger of electric shock Disconnect the device Cover up live parts 5 1 Fitting and electrical connection...

Страница 5: ...azardous voltages in the connec tion area The total load of the outputs can be subdivided as desired Do not exceed the total rated current Do not connect any other products to the bus output This migh...

Страница 6: ...g to the connection example Figure 5 L N L N PE max 2 A Figure 5 Application example signal lamp for optical operating display Connect the KNX binary input according to the connection example Figure 6...

Страница 7: ...s line length between two KNX bus subscribers Max 700 m 6 Technical data Rated voltage AC 220 240 V The device is operable in the range of 180 V AC 264 V AC Mains frequency 50 60 Hz Power loss max loa...

Страница 8: ...nnection mode device connection terminal Finely stranded with conductor sleeve 0 5 2 5 mm 7 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade Please...

Отзывы: