Triple control unit 1-10 V

Installation Instructions

Triple control unit 1-10 V

10/05

Page 1 of 3

System information

This unit is a product of the Instabus-EIB-System and 
corresponds to the EIBA Guidelines. Detailed techni-
cal knowledge acquired in Instabus training courses 
is a prerequisite for the understanding of the system. 
The functions of the device are software-dependent. 
Detailed information on the software and the func-
tions implemented and the software itself are avail-
able from the manufacturer’s product data bank.

Planning, installation and commissionning of the de-
vice are effected with the help of EIBA-certified soft-
ware.

For the productdatabase and technical descriptions 
please refer to the Gira Datenpool CD, order no. 
1992 10, or to the internet at www.gira.de offering up-
to-date information.

Function

The control unit reveives telegrams transmitted via 
the Instabus EIB and switches or dims fluorescent 
lamps in combination with electronic ballasts. During 
dimming, the electronic ballast is controlled from a 
1-10 V interface. Switching is effected by a relay con-
tact that switches the ballast’s voltage supply on and 
off. This contact can also be actuated manually with-
out any effect on the bus.

Characteristics

• Connection of different phases to terminals A1 – 

A3.

• Switching and dimming behaviour presettable with 

parameters.

• Checkback for switching status.
• Transmission of brightness value.
• Soft-On, Soft-Off and delayed dimming presettable 

with parameters.

• Light-fading mode and immediate brightness 

change.

• Lightscape operation possible.
• Behaviour on bus voltage return presettable.

Important information

• The number of electronic ballasts that can be 

dimmed via the 1-10 V interface, depends on the 
ballast-specific load current of the types used.

• Please observe: electronic ballasts produce high 

peak currents during switch-on, which might cause 
the relay contacts to stick together. For loads up to 
max. 200 VA per channel we recommend using an 
inrush current limiter (Art.no. 0810 00).

• For greater loads we recommend using separate 

load-switching relays.

Triple control unit 1-10 V

Order no.: 1017 00
Order no.: 1019 00

Safety warnings

Attention: Electrical equipment must be installed 
and fitted only by qualified electricians and in ob-
servance of the applicable accident prevention 
regulations.

To prevent electric shocks, disconnect the pow-
er supply before working on the device (by cut-
ting out the circuit breaker).

Any non-observance of the fitting instructions 
may cause fire or other hazards.