7.5.5 Power Control
1. Set output power 2. Set Reactive Power 3. Out_P With Restore
4. Rea_P With Restore 5. Select PF Curve
This function is applicable f
or
maintenance personnel only, wrong settings
will prevent the inverter from reaching maximum power.
7. Operation
Maintenance or replacement could clear or cause a different value for total energy. Use this
function to allow user to revise the value of total energy to the same value as before. If
the monitoring website is used the data will be synchronous with this setting automatically.
(see Figure 7.20).
Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the
ENTER key to execute the setting. Press the ESC key to return to the previous menu.
7.5.6 Calibrate Energy
Figure 7.20 Calibrate energy
YES=<ENT> NO=<ESC>
Energy:0000000kWh
7. Operation
Special settings have the submenu shown below:
7
.
5.7 Special settings
1. Grid Filter Set 2. Relay_Protect Set 3. ILeak_Protect Set
4. GROUND_Protect Set 5. GRID INTF.02 Set 6. MPPT Parallel Mode
7.
Cnst.
Voltage
Mode 8. L/FRT
Set 9. IgZero_COMP. Set 10. PI
Set
11. IgADCheckPRO Set 12. NoSmallPulse Set
This function is applicable by maintenance personnel only.
7.5.8 S
TD
.
Mode
Settings
This function is applicable by maintenance personnel only.
.37.
.36.
7.5.9 Restore Settings
Figure 7.21
Press the ENTER key to save the setting. Press the ESC key to return to the previous menu.
Restore
Settings resets the inverter to factory defaults. Selecting will show the
screen below:
This function is applicable to maintenance personnel only.
Are
you
sure
?
YES
=<
ENT
>
NO
=<
ESC
>
Solis inverter could set different work mode to work with different grid requirement.
There are 5 items under STD mode setting.
1. Working Mode Set 2. Power Rate Limit 3. Freq Derate Set
4. 10mins Voltage Set 5. Initial Settings.
There are 6 items in working mode submenu.
1. NULL,Volt-watt 2. Volt-var 3. Fixed-PF 4. Reac-power 5. Power-PF
There are 2 items in power rate limit submenu.
1. Power Rate: 0-100% 2. RateP_Sts-US: stop/run
There are 3 items in Freq Derate Set submenu.
1. over Freq 2. under Freq 3. Derate mode.
There are 5 items in initial setting submenu.
1. Work mode default 2. Power rate default 3. Fre Derate Default
4. 10mVvoltage Default 5. DRM ON/OFF
There is 1 item in 10mins voltage set submenu.
1. 10mins voltage
:
244-258V.