Warning:
2) Prepare OT terminals: M6.
5.3.1 Protective ground wire connection(PE)
1) Prepare the grounding cable: recommend to use the 16~35mm
²
outdoor
copper-core cable.
B (insulation stripping length) is 2mm~3mm longer than A (OT cable
terminal crimping area) 2mm~3mm.
Figure5.7 suitable length
Important:
Important:
A
B
No matter what kind of grounding connection is adopted, it is strictly forbidden to
connect the ground of the inverter with the lightning protection of the building ,
otherwise Solis will not be responsible for any damage caused by lightning.
5.
Installation
5.
Installation
In order to improve the corrosion resistance of the grounding terminal, we
recommend that the External grounding terminal should be coated with
silica gel or paint for protection after the installation of the grounding cable.
Important:
Figure5.9 fix the cable
Figure5.8 strip wire
After crimping the terminal to the wire, inspect the connection to ensure the
terminal is solidly crimped to the wire.
5) Remove the screw from the heat sink ground point.
6) Use the screw of the ground point to attach the grounding cable.
Tighten the screw securely. Torque is 3Nm (as shown as in Figure 5.9).
Important:
.17.
.16.
To effectively protect the inverter, two grounding methods must be performed.
Connect the AC grounding cable(Please refer to section 5.3.3).
Connect the external grounding terminal.
To connect the grounding terminal on the heat sink, please follow the steps below: