6.5.2 Grid ON/OFF

This function is used to start or stop the generation of Solis three phase inverter  

(see Figure 6.12).

      Grid ON

        Grid OFF

Figure 6.12 Set Grid ON/OFF

Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key 

to execute the setting. Press the ESC key to return to the previous menu. 

6.5.3 Calibrate Energy

Maintenance or replacement could clear or cause a different value of total energy. Use this 

function could allow user to revise the value of total energy to the same value as before. If 

the monitoring website is used the data will be synchronous with this setting automatically. 

(see Figure 6.13).

Figure 6.13 Calibrate energy

Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the 

ENTER key to execute the setting. Press the ESC key to return to the previous menu. 

YES=<ENT> NO=<ESC>

Energy:0000000kWh

6. Operation

6. Operation

.27.

NOTE: 

There are two stage for voltage and frequency limits in User-Def, please 
make sure limit 1 is in the scope of limit 2, otherwise the set will be failed.
The initial values of the User-Def standard are some reference values. They 
are not indicating the values of the standard you are currently using.

Press the UP/DOWN keys to scroll through items. Press the ENTER key to edit the highlighted 

item. Press the UP/DOWN keys again to change the setting. Press the ENTER key to save the 

setting. Press the ESC key to cancel the change and return to the previous menu.

NOTE: 

It must set Grid ON (refer to Section 6.5.2) before the new standard can 
be used.

For Solis-6K-LV/Solis-10K-LV

 

OV-G-V1: 220---288V

OV-G-V1-T: 0.1---9S

OV-G-V2: 220---288V

OV-G-V2-T: 0.1---1S

UN-G-V1: 160---210V

UN-G-V1-T: 0.1---9S

UN-G-V2: 160---210V

UN-G-V2-T: 0.1---1S

OV-G-F1: 50.2-53Hz(60.2-63Hz)

OV-G-F1-T: 0.1-9S

OV-G-F2: 51-53Hz(61-63Hz)

OV-G-F2-T: 0.1-9S

UN-G-F1: 47-49.5Hz(57-59.5Hz)

UN-G-F1-T: 0.1-9S

UN-G-F2: 47-49Hz(57-59Hz)

UN-G-F2-T: 0.1-9S

Below is the voltage and frequency protection limits range for Solis three phase PV 

inverter:

                   

              For Solis-6K/Solis-10K/Solis-15K/Solis-20K-HV 

                 

             OV-G-V1: 410---530V                                OV-G-F1: 50.2-53Hz(60.2-63Hz)

             OV-G-V1-T: 0.1---9S                                  OV-G-F1-T: 0.1---9S

             OV-G-V2: 430---580V                                OV-G-F2: 51-53Hz(61-63Hz)

             OV-G-V2-T: 0.1---1S                                  OV-G-F2-T: 0.1---9S

             UN-G-V1: 300---360V                                UN-G-F1: 47-49.5Hz(57-59.5Hz)

             UN-G-V1-T: 0.1---9S                                  UN-G-F1-T: 0.1---9S

             UN-G-V2: 230---330V                                UN-G-F2: 47-49Hz(57-59Hz)

             UN-G-V2-T: 0.1---1S                                  UN-G-F2-T: 0.1---9S

.26.

Содержание Solis-10K

Страница 1: ...PV Grid Tie Inverter Installation and Operation Manual Ver 2 6 Solis Three Phase Inverter...

Страница 2: ...ont Panel Display 3 2 LED Status Indicator Lights 3 3 Keypad 3 4 LCD 4 Installation 4 1 Selecting Location for the Inverter 4 2 Mounting the Inverter 4 3 Electrical Connections 5 Start and Stop 5 1 St...

Страница 3: ...240V three phase grid system All 6 models are transformerless topology grid tie PV inverter Figure 1 1 Front side view 3 Figure 1 2 Bottom side view 6 Operation 6 1 Main Menu 6 2 Information 6 3 Sett...

Страница 4: ...WARNING symbol indicates important safety instructions which if not correctly followed could result in serious injury or death Improper use may result in potential electric shock hazards or burns This...

Страница 5: ...The inverter must be installed according to the instructions stated in this manual 5 The inverter must be installed according to the correct technical specifications 6 To startup the inverter the Gri...

Страница 6: ...fault indications 8 9 To select a location for the inverter the following criteria should be considered To avoid over heating ambient air temperature MUST be considered when choosing the inverter ins...

Страница 7: ...500mm 500mm 500mm 500mm Figure 4 1 Inverter Mounting clearance 4 Installation 4 Installation Inverter should be mounted in a vertical position as shown in Figure 4 3 The steps to mount the inverter on...

Страница 8: ...itting the hooks into the slot of the bracket Use M4 14 stainless steel screws at holes E and F in Figure 4 to secure the mounting hooks to the rear of the inverter Figure 4 4 Wall Mount Bracket The e...

Страница 9: ...4 8 Insert the Wire into the Connector Cap nut and contact pin Figure 4 10 Connector with Cap nut Screwed on Figure 4 11 Connect the DC Connectors to the Inverter v Then connect the DC connectors to t...

Страница 10: ...of AC wire about 8mm Insert the cable through the jacket and cap nut of connector then insert the wires to the grid terminal and tighten the screws on the connector as shown in Figure 4 13 Please try...

Страница 11: ...Solis 15K Figure 5 1 Company Name and Inverter Model on LCD 3 When both the DC and the AC grid sides supply to the inverter it will be ready to generate power Initially the inverter will check both i...

Страница 12: ...n by scrolling up or down 6 Operation Pressing the ESC key returns to the Main Menu Pressing the ENTER key to lock Figure 6 2 a or unlock Figure 6 2 b the screen V_DC1 350 8V I_DC1 5 1A V_DC2 350 8V I...

Страница 13: ...cation purpose The address number can be assigned from 01 to 99 see Figure 6 4 The default address number of Solis three phase inverter is 01 6 Operation 23 22 6 4 Advanced Info Technicians Only Selec...

Страница 14: ...E Before to using this function please set GRID OFF to stop inverter refer to Section 6 5 2 NOTE The inverter is customized according to the local standard before shipping to the customer The User Def...

Страница 15: ...ues of the User Def standard are some reference values They are not indicating the values of the standard you are currently using Press the UP DOWN keys to scroll through items Press the ENTER key to...

Страница 16: ...Trouble Shooting Alarm Message OV G V UN G V OV G F UN G F G IMP NO GRID OV DC OV BUS UN BUS GRID INTF INI FAULT OV TEM GROUND FAULT Failure description Over grid voltage Under grid voltage Over grid...

Страница 17: ...59 3 AS4777 VDE 0126 1 1 VDE 4105 CEI 0 21 CQC 31 30 9 Specifications Operating Range Utility Frequency Model The max DC input voltage MPPT operation range The max dc input current Number of MPPT stri...

Страница 18: ...rent Rated grid frequency Max Efficiency Protection Size mm Weight Topology Internal consumption Running temperature Ingress protection Interface Design lifetime Utility Monitoring Operation Surroundi...

Отзывы: