Gillette SPH-120 Скачать руководство пользователя страница 4

 

PAGE 4

 

NOTICE

 

 

 For all safety reasons to the equipment, GILLETTE 

recommends installation, start-up and service be per-
formed by experienced personnel. 
 

 Sufficient, un-obstructed flow of cooling air is criti-

cal for correct generator operation. 
 

 The generator must be installed outdoors, away 

from an over-hang roof where ice and snow could 

avalanche onto generator and away from sprinklers 
that could throw water up into cooling vents of gen-
erator. 

 

 Electric load applied to generator should be no 

more that 75% of generator maximum rating to avoid 
constant maximum generator load use. 

 

 Generator should not be exposed to excessive and 

constant moisture, dust, dirt, or corrosive environ-

ments. 
 

 If connected loads cause over heating or excessive 

vibration, an overload condition exists.  Remove 

loads until condition stabilizes. 
 

 Do not sit, step, or load heavy items on generator 

roof.  Added stress can cause breakage. 
 

 Do not start generator with air cleaner, air cleaner 

cover, or oil dipstick removed, nor with oil drain hose 

in open drain position. 
 

 Keep a fire extinguisher rated “ABC” close by your 

generator and be familiar on how to use it.  Consult 

your local fire department, for additional fire preven-
tion ideas. 
 

  Be  sure  that  a  positive  manual  fuel  valve  be  in-

stalled in fuel line feeding generator. 
 

 Do not tamper with engine controls, generator is 

factory adjusted to supply rated voltage and speed. 
 

 Never operate generator when ambient tempera-

ture is over 105º F, as electrical insulation system may 
fail. 
 
 

 
 
 

STARTING BATTERY PRECAU-

TIONS 

 

Starting batteries are not furnished with 
your generator set, but they are available 
through your installing contractor.  The 
home standby generator requires a Group 

36, 12 VDC fully charged battery with mini-
mum 390 cold cranking amps. 

 

 Released battery electrolyte can burn your skin 

and eyes and is toxic. 
 

 When electrolyte touches skin, wash it off immedi-

ately with water and seek medical attention.  When 
electrolyte contacts eyes, flush thoroughly with water 
and seek medical attention. 
 

 Spilled electrolyte must be washed away with an 

acid neutral agent.  Use a solution of one pound bicar-
bonate of soda to one gallon of water, and wash down 

acid effected areas until evidence of acid foaming 
reaction has ended. 
 

 A battery provides risk of electric shock.  Remove 

watches, rings, or other metal items when working 
with batteries.  Use tools with insulated handles. 
 

 When disconnecting battery cables, always dis-

connect the battery charger first, the positive battery 
cable second, and negative battery cable last.  When 
reconnecting cables, always reconnect the positive 

battery cable first, then negative cable, and recon-
nect battery charger last, to reduce possible arching. 
 

 Discharge body static electricity by touching a 

grounded metal surface on generator before touching 
battery. 
 

 Do not dispose of batteries in a fire and do not 

open or mutilate a battery, as the battery is capable of 
exploding. 
 

 Lead acid batteries present a risk of fire or explo-

sion because they generate hydrogen gas, within.  Do 
not smoke, nor have flame or spark in a battery area. 

 

 

WARNING 

 

The engine exhaust from this product contains 

chemicals known to the state of California to cause 
cancer, birth defects, or other reproductive harm. 

WARNING

 

Содержание SPH-120

Страница 1: ...OPERATION AND INSTALLATION GUIDE FOR MODELS SPS 100 SPH 120 SPS 120 SPV 160 GILLETTE GENERATORS AUTOMATIC POWER SYSTEMS...

Страница 2: ...tural Gas NG 12 13 Gaseous Dry Fuel System Liquid Propane Gas LPG 14 15 Prepare for Generator Operation 15 18 Access to Interior Battery Selection Installation Electricians Wiring Installation Final P...

Страница 3: ...procedure is used and is not recommended by GILLETTE the person or company responsible for the generator modification must assume all responsibility for safety and correct operation for the operator s...

Страница 4: ...AU TIONS Starting batteries are not furnished with your generator set but they are available through your installing contractor The home standby generator requires a Group 36 12 VDC fully charged batt...

Страница 5: ...running engine produces a poisonous gas from its muffler exhaust pipe This is an odorless in visible and colorless poison that cannot easily be detected Breathing carbon monoxide will cause fa tigue h...

Страница 6: ...ical output shows sparks smokes emits flames vibrates or shows any other abnormal operation Do not modify generator design Do not modify carburetion system as it is factory set for C A R B EPA emissio...

Страница 7: ...ibility of the sepa rate manufacturers of the ATS PRE INSTALLATION PLANNING The beginning installation requires some thought and planning The following illustrations are meant to fa miliarize reader w...

Страница 8: ...ther air intakes should be minimum 10 feet from exhaust end 6 Windows and doors on adjacent walls to be closed at all times during generator operation 7 Nearest roof overhang vent should be 10 feet fr...

Страница 9: ...best place for these two neutrals to meet generator and utility neutral is in the auto matic transfer switch However still connect gen set mechani cal ground to the stake All factory gen sets have a...

Страница 10: ...with the entire generator set 11 12 VDC battery charger Installer must connect 120 volt 1 phase utility power to this charger 12 Oil drain with flexible drain hose NOTE Change oil after every 50 hour...

Страница 11: ...to normal operation C Hour Meter Total hours of use and is used as service reminder D Main Line Circuit Breaker UL 146 circuit breaker will trip open upon short circuits or overloads KNOWYOUR SYSTEM C...

Страница 12: ...sure must be 6 to 8 inches water column 4 to 4 ounces and minimum 1000 BTU rating per cubic foot hour Figure 1 BTU Values based on 1000 BTU s per cubic foot Gas supplier may need to know Nat Gas consu...

Страница 13: ...l new installations plus any future repair or troubleshooting procedures must include a natural gas manometer test This test should be conducted after all other natural gas appliances have been turned...

Страница 14: ...135 cu ft can be de livered over a 50 ft distance with a 1 diameter fuel pipe INSTALLER S RESPONSIBILITY Use Figure 4 chart to learn cubic feet hour value of generator to be installed Use Figure 5 cha...

Страница 15: ...LPG tank are reasonably close 20 Ft to 50 Ft as it results in short runs for both electric wires and LPG fuel lines When these two identities are far apart always choose to locate generator as close t...

Страница 16: ...jobsite A fully charged battery must test at 12 5 13 0 volts DC Also the correct battery for models SPH 85 SPH 100 SPH 120 and SPV 160 must have lug terminals to match lug battery cables for a bolt to...

Страница 17: ...tery charger before working on battery terminals A battery can cause a chemical burn Before working on a battery follow safe procedures Wear full eye protection and protective clothing When battery el...

Страница 18: ...unction The generator will not ex ercise in this position TEST position will start the engine but will not dis connect utility power from the transfer switch This position is used for testing the gene...

Страница 19: ...re position this LPG venture For natural gas operation remove the carburetor flexible fuel line from LP stamped brass fitting and dead end brass cap from NG stamped brass fitting Attach fuel line to...

Страница 20: ...r switch ATS STEP 2 Turn the MODE SELECTOR switch located on the control panel from OFF RESET position to TEST position This will establish the first engine start cycle With the ENGINE RUNNING lamp lo...

Страница 21: ...rong enough to perform under this demanding scenario However if the load is 75 or more induc tive large motors UPS systems large air condition ers it may be necessary to install a time delay de vice a...

Страница 22: ...or Inspect the debris guard on engine air intake to insure no obstructions have accumulated Inspect radiator liquid cooled sets to insure no debris accumulation has occurred Some generator models have...

Страница 23: ...L CONNECTION THERE ARE TWO KNOCK OUT HOLES ON THE RIGHT HAND SIDE OF GENERATOR END BOTH HOLES ARE FOR 3 4 CONDUIT GENERATOR END VIEW CONTROL DOOR PANEL THIS PANEL IS HERE TO HELP WITH INITIAL WIRING I...

Страница 24: ...POLY BASE AS SHOWN USING 5 16 18 HEX NUT TO LOCK BOLT IN PLACE INSTALL GEN SET AND METAL BASE ONTO EXTENEDED 5 16 18 BOLT AND SECURE WITH LARGE FLAT WASHER AND HEX NUT CAUTION TIGHTEN NUT ONLY TO HOLD...

Страница 25: ...IS A 3 4 THREADED PIPE FOR CONNECTION ELECTRICAL CONNECTION THERE ARE THREE PLUGGED HOLES ONE ON THE RIGHT HAND SIDE AND ONE ON THE LEFT HAND SIDE OF GENERATOR END BOTH HOLES ARE FOR 3 4 CONDUIT FULL...

Страница 26: ...NOT ENERGIZED GAS REGULATOR NOT OPENING SPARK PLUG IS DEFECTIVE OR SPARK PLUG WIRE IS DEFECTIVE OR DISCONNECTED VENTS IN GAS REGULATOR IS PLUGGED UP C ENGINE RUNS ERRATIC AIR CLEANER IS DIRTY AND NEED...

Страница 27: ...START STOP HIGH TEMPERATURE DRY START STOP CONTACTS FROM OTHER EQUIPMENT NEUTRAL ENCLOSURE GROUND MECHANICAL GROUND LOAD SIDE 120 240 VAC AND NEUTRAL CONNECT TO TRANSFER SW GROUND STAKE FOR CONTROLLE...

Страница 28: ...LINES X YEARLY FUEL LINES X YEARLY CONNECTOR JOINTS X YEARLY EXHAUST MUFFLER X EVERY 6 MONTHS SPARK ARRESTOR X EVERY 6 MONTHS FLEX LINE X EVERY 6 MONTHS LEAKAGE X EVERY 6 MONTHS JOINT CLAMPS X EVERY 6...

Страница 29: ...g table to keep a record of all periodic and unscheduled maintenance and service See Ser vice Schedule Record the name address and phone number of your authorized GILLETTE service center DATE HOUR MET...

Страница 30: ...5 OWN 794 20080828 Gillette Generators Inc 1340Wade Drive Elkhart IN 46514 Phone 574 264 9639 Fax 574 262 1840 E mail sales gillettegenerators com www gillettegenerators com Call for Tech Support 1 86...

Отзывы: