Page 6-9
Troubleshooting Tools
Troubleshooting and Analysis
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
When the VaporTEK Pump Unit starts running (> 5 LPM), the fuel flow and the related motor
speed information are shown on the terminal screen. Motor activation using M1 and M2
HV
inputs
do not support this debug mode. Use “s” mode to obtain the speed and power
information. Press “
s
” in order to show the power consumption data of the motor.
Figure 6-13: Terminal Screen
15
Press
5
to show the calibration table. The factory set calibration table is displayed when
connected for the first time; thereafter, the table shows the latest calibrated table values created
by autocalibration.
Figure 6-14: Calibration Table