Page 5-15
OPW 12VW Nozzle - Wet Calibration
VaporTEK Calibration Start-up Sequence
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
10
Compare the fuel and vapor total results of transaction. Calculate the A/L-Ratio as follows:
A/L [%] = Vapor [FB1-Total] / Fuel Volume [Dispenser Display] x 100%
Figure 5-29: Calculating A/L Ratio