I0680001/06-2016
27
10. Programming the actuator
10.1.
Opening stroke-end
The opening stroke-end of the actuator can be adjusted by selecting the dip-switches
located inside the actuator underneath the black rubber plug (T)
(see fig. below)
, near
the label that indicates the state of the dip-switches.
The setting can be made very easily by selecting the dip-switches as specified in the
table below.
STROKE
(mm)
DIP-SWITCH
WITHOUT
ELECTROMECHANICAL
LOCK
WITH
ELECTROMECHANICAL
LOCK
1
2
3
4
4
70
ON
OFF
OFF
OFF
ON
125
OFF
ON
OFF
170
OFF
OFF
ON
210
OFF
OFF
OFF
The actuator is factory-set with the longest stroke (210 mm).
10.2.
Closure stroke-end
The stroke-end at closure is automatic and cannot be programmed.
The actuator stops when the charge is absorbed when the window is completely
closed and the weather stripping is completely depressed, or when the charge
absorbed is more than 15% of the nominal charge.
After each closure or intervention of electronic protection devices, the chain will move
about 1 mm in the opposite direction to give correct compression to the seals and
release the mechanical parts.
10.3.
Operation with electromechanical lock
The actuator can also work in combination with the electromechanical lock; this
operating mode can be selected using dip-switch No.4. If the dip-switch is set on ON
without the lock being connected, the actuator will not move.