Subject to alterations, 03.06.20
19/32
Start-up and calibration
LMV phase display
Display
Description
Ph00
Fault phase
Ph01
Safety phase
Ph10
Go home
Ph12
Standby (stationary)
Ph22
Blower start-up time (blower motor = ON, safety valve = ON)
Ph24
Run in pre-air position
Ph30
Pre-air time
Ph36
Run in ignition position
Ph38
Pre-ignition phase
Ph39
Leakage check filling time (test pressure switch min for installation between fuel valve 1 and
fuel valve 2)
Ph40
First safety time (ignition transformer ON)
Ph42
First safety time (ignition transformer OFF)
Ph44
Interval 1
Ph50
Second safety time
Ph52
Interval 2
Ph60
Operation 1 (stationary)
Ph62
Maximum time small-load setting (operation 2, preparation decommissioning, run in small-load
setting)
Ph70
After-burn time
Ph72
Run in post-ventilation position
PH74
Post-ventilation time (no external leak test)
Ph78
Post-ventilation time (abort when power controller ON)
Ph80
Leakage check idle time
Ph81
Leakage check test time atmospheric pressure, atmosphere test
Ph82
Leakage check filling test, filling
Ph83
Leakage check test time gas pressure, pressure test
Ph90
Gas shortage waiting time