22
2
A1Fn
Alarm 1 function:
+1: Acknowledge alarm
+2: Delayed alarm
+4: Latch alarm
+8: No alarm at power on
+16: No alarm at set-point change
Range: 0-31
default: 0
3
A1Lo
Alarm 1 low level
Range: -1999 to A1th
default: -1999
4
A1th
Alarm 1 Threshold
Range: A1Lo to A1Hi
default: 0
5
A1hi
Alarm 1 high level
Range: A1th to 9999
default:9999
6
A1hY
Alarm 1 hysteresis
Range: OFF to 9999
default: 1
7
o1LV
Output 1 low value
Range#
1,2,3,4
:0.0%to o1HV
Range#
5,6,7,8
: -100.0% to o1HV
default: 0.0
8
o1hV
Output 1 high value
Range: o1LV to 100.0 %
default: 100.0
9
o1hs
Output 1 hysteresis
Range: OFF to 100.0 %
default:1
10
A1dL
Alarm 1 delay
Range: OFF to 9999 s
default:OFF
Menus for Alarm 2 are same as for Alarm 1.
MAIN MENU:
REG(Regulator)
Parameter
Description
1 cont
Controller
type:
Range:
1.onFS:On-Off Symmetric
2.onFA:On-Off Asymmetric
3.PId: PId Controller
4.nr:neutral zone ON–OFF
default: PID
2 Func
Controller
type:
Range:
1.hEAt:Reverse acting
2.cooL:Direct acting
default :hEAt
3
hESt
Hysteresis for On-Off controller
Range: OFF - 9999
default: 1