14.2 Holdback (hbck):
14.2.0 Holdback In Ramp:
While in ramp mode if the difference between SP and PV value goes beyond Holdback
value, the SP ramping stops and it is held on the given value as long as PV < (SP-hbck)
OR PV > (SP+hbcK) range.
14.2.1 Holdback In Soak:
While in Soak mode if the difference between sP and Pv value goes beyond Holdback
value, the soak timing is stopped and it is resumed when PV comes back within (SP-
hbck) and (SP+hbcK) range.
15.0 Soft Start :
All parameters referring to the soft start functioning are contained in the group “rEg”.
The soft start functioning allows limitation of output power when instrument is switched
on for a limited period of time. Following parameters are needed:
“sst” - Soft start time in hh: mm
“ssth” - soft start threshold
“ssP” - soft start power
Soft start functionality will abort when sst or ssth whichever earlier is met.
16.0 ALARMS:
16.1 Alarm Types:
1.Absolute low (“AbLo” on display):
Alarm is activated if PV goes below A1th and is deactivated if PV goes above
(A1th+A1hY).
2.Absolute high (“Abhi” on display):
Alarm is activated if PV goes above A1th and is deactivated if PV goes below (A1th-
A1hy).
3.Absolute band (“AbbA” on display):
Alarm is activated if PV goes above A1hi or below A1Lo. It is deactivated if it goes below
(A1hi-A1hy) or above (A1Lo+A1hy).