PROFESSIONAL AUTOMATIC SYSTEM FOR GATES AND GARAGEDOORS
4
3
FUNCTION SELECTION VIA DIP-SWITCH SW1
The following table shows what occurs each time a START COMMAND is given depending on the program selected and the state in which
the gate is at that moment.
(*) DEFAULT SETTINGS
Turning the trimmers clockwise increases the AMPEROMETRIC LOCKING THRESHOLD of the respective motor (2.5 to 5.5 A).
The intervention of the current limiter both during opening and closing causes an immediate stop of the movement.
DEFAULT SETTINGS: trimmers adjusted to half their stroke.
ADJUSTING THE TRIMMERS PT1 (motor 1) and PT2 (motor 2)
If the control unit is coupled to the receiver code AU01780 it is also possible to control partial opening of only
WING 1
(pedestrian cycle) using
the 2nd channel of the remote control (
previously stored
).
To program the
PEDESTRIAN CYCLE
operate as described above (steps 1, 2, 3, 5, 6, 7, 8), but give the command through the
2nd CHANNEL
of
the remote control.
DIP
ON
OFF
Water Hammer enable to facilitate electric lock release
STEP-BY-STEP
program (*)
CONDOMINIUM program
DECELERATION phase in the last seconds of each
manoeuvre (*)
2
(Only with DIP1 OFF)
1
Water Hammer disabled (*)
RESIDENTIAL
program
(step-by-step with automatic reclosing)
Uninfluential (see DIP2) (*)
DECELERATION disabled
6
5
PHOTOCELL input disabled (terminals 1-4) (*)
TIME PROGRAMMING
PHOTOCELL input enabled
Normal operation (*)
CONDOMINIUM
PROGRAM
selected
The gate is
CLOSED
OPENS
OPENS
OPENS
RESIDENTIAL
STEP-BY-STEP
The gate is
OPENING
STOPS and enables
counting of the pause
time for the next
automatic reclosing
STOPS
IGNORED
The gate is
OPEN
CLOSES
(the gate would close
automatically at the end
of the pause time)
CLOSES
Reinitialises counting of
the pause time at the
end of which it closes
automatically
The gate is
CLOSING
STOPS AND RE-OPENS
STOPS
STOPS AND RE-OPENS
WARNING:
With DIP2 OFF: should the power fail during opening, closing or pause, when the power is restored the control unit automatically per forms a full
closing manoeuvre of the gate.
WARNING !
To facilitate the PROGRAMMING phase, let the control unit or the receiver learn a remote control (see CODE LEARNING), otherwise the START
command must be given by closing the contact to the terminals 3-4.
Start programming from the condition in which the GATE IS COMPLETELY CLOSED.
To enable deceleration set DIP3 to ON before starting to program.
(run time, pause time, gate phase shift time, pedestrian cycle)
1) GATE CLOSED: set DIP5 to ON.
2) Press START: Wing 1 star ts opening and after 2 seconds also Wing 2.
3) When Wing 1 arrives against the mechanical stop, it stops automatically.
WING 1 STOPS
.
4) When Wing 2 arrives against the mechanical stop, it stops automatically.
WING 2 STOPS
.
5) The flashlight goes off and counting of the pause time star ts. After the desired time (max. 240 s) press START:
WING 2 STARTS CLOSING
.
6) Wait for the time necessar y to assure the desired gate phase shift and then press START:
WING 1 STARTS CLOSING
.
7) The control unit does not accept any more commands until the
WINGS HAVE STOPPED
against the respective mechanical closing stops.
7)
GATE CLOSED
.
8) Set DIP5 to OFF to finish programming.
TIME PROGRAMMING