battery  is  full,  according  to  the  formula  above,  the  battery  use  time  =200(AH)/ 
(400/12x110%) = 5.4 (Hour). This means the battery can be used for 5.4 hours.

Notice:

 The nominal battery capacity is the discharge capacity in 20 hours discharge 

rate ,under the condition when the discharge current exceeds this value, the discharge 
capacity will be reduced, the corresponding discharge time will be shortened than the 
calculation  value,  this  part  of  the  specification  can  refer  to  battery  manufacturer,  and 
whether the battery fully charged will also affect the results.

6. CONNECTION

1). Grounding
      The power inverter has a terminal on the back panel marked "Grounding" or "      ". 

This is used to connect the chassis of the power inverter to the ground.The ground 
terminal has already connected to the ground wire of AC output receptacle through 
the internal connecting wire. The ground terminal must be connected to the ground 
wire, which will vary depending on where the power inverter is installed. In a 
vehicle, connect the ground terminal to the chassis of the vehicle. On the ship, 
connect the ground terminal to the ship grounding system; In a fixed position, 
connect the ground terminal to the earth.

Warnings:

 To make sure the firmness of the connection. The ground wire must be 14AWG 

2

(2.08mm  )or even larger.

 Do not operate the power inverter without connecting to ground. Electric shock 

hazard may result. 

2). Connect to the battery
(1).Please do all the safety precautions before connection, then check whether the 

battery voltage is in accordance with the input voltage of the inverter. Only the 
voltage of battery according with the requirements can be allowed to connect with 
the inverter.

(2).The connecting wire must be big enough to bear current, or else the inverter can 

not support big load because of voltage reduce caused by the small cross-
sectional wire. Depending on the below table, please select the input DC wire or 
larger one.

Rated voltage 
of inverter

Current max. 
load power

Max. current 
of wire

Specification of
wire length

1m

Specification of
wire length

1m

Specification of
wire length

N m

1200W

1500W

2000W

2500W

3000W

1200W

1500W

2000W

2500W

3000W

12V

6AWG

(13.3mm )

2

4AWG

(21.15mm )

2

3AWG

(26.67mm )

2

2AWG

(33.62mm )

2

1AWG

(42.41mm )

2

N×6AWG

(N×13.3mm

2

)

N×4AWG

(N×21.15mm

2

)

N×3AWG

(N×26.67mm

2

)

N×2AWG

(N×33.62mm

2

)

N×1AWG

(N×42.41mm

2

)

3AWG

(26.67mm

2

)

1AWG

(42.41mm

2

)

0AWG

(53.49mm

2

)

00AWG

(67.43mm

2

)

000AWG

2

(85.01mm )

24V

100A

150A

200A

250A

300A

50A

75A

100A

125A

150A

9AWG

(6.63mm )

2

7AWG

(10.55mm )

2

6AWG

(13.3mm )

2

5AWG

(16.77mm )

2

4AWG

(21.15mm )

2

N×9AWG

(N×6.63mm

2

)

N×7AWG

(N×10.55mm

2

)

N×6AWG

(N×13.3mm

2

)

N×5AWG

(N×16.77mm

2

)

N×4AWG

(N×21.15mm

2

)

6AWG

(13.3mm

2

)

4AWG

(21.15mm

2

)

3AWG

(26.67mm

2

)

2AWG

(33.62mm

2

)

1AWG

(42.41mm

2

)

Notice:
1. The above table is only for your reference. In practice, the thick wire can be replaced 

by two thin parallel wires if only the total section acreage of the wire meets the 
requirements. 

2.In high current, the input DC wire may produce voltage drop, therefore, the operating 

voltage should be subject to the value on the terminals. If the voltage drop is too 
large, it can increase the acreage of the section or reduce the length of the lead. The 
recommended length of lead is less than 1m.

3.Connect cathode wire of the battery to the cathode terminal (black) on the back panel 

of inverter and then connect the anode wire of the battery to the anode terminal (red) 
on the inverter, and fix them.

Warnings:

1) Please wear eye patch and work clothes when working around the battery to avoid 

the acid and corrosive objects harm your eyes and skin.

2)  Prepare  enough  water  and  soap.  In  case  the  acid  materials  contact  eyes  or  skin, 

clean  it  by  soap  and  water  as  soon  as  possible.  If  the  acid  materials  spay  to  your 
eyes accidentally, clean it by cold water immediately and then sent to hospital.

3) Do not put any combustible material in the location of installation for spark will result 

when it is connected to the battery.

4)  Keep  good  ventilation.  The  battery  may  produce  a  little  inflammable  gas  when  it 

works,  so  keep  away  from  the  inverter  and  it  is  better  to  install  them  in  different 
space.

5)  Fix  the  connecting  wire  of  the  input  DC,  or  it  will  result  the  over-reduction  of  the 

voltage or over-temperature of the wire.

6) Reverse connection of the polarities or the short circuit will burn the fuse or result the 

permanence damage of the internal elements of inverter.

7) Take away the metal accouterment, such as ring or watch, when installation to avoid 

the short circuit.