If all of the above methods have been tried, the product still not work properly. 
The internal circuit of the product may be out of order. Please return the 
product to the supplier for maintenance.

12. TROUBLESHOOTING TIPS

Reduce a load power,or turn on the 
appliance first, then turn on the 
inverter. The inverter internal soft-start 
circuit to buffer start the appliances.

1. Cut off the load and allow to cool for 

10 to 30 minutes. Restart after it 

reaches to normal temperature. 

2. The load power is too large. Reduce 

the total load power to the range of 

rated power. 

3. Avoid blocking the vent and improve 

the ventilation condition.

4. Reduce the ambient temperature. 

1. Use a true RMS multimeter to measure, 
such as the model FLUKE 177/179.
2.Try to maintain the input voltage in the 
range of rated power 
3.Change the battery of the multimeter 
then test again.

1. Do not use when the battery is 
charging. 
2. Check the rated voltage of the battery 
and make sure that it is in the allowable 
range of the input voltage. 

1. Measured using true RMS 
multimeter.
2. The battery power of RMS 
Multimeter is low.
3. The input voltage is too 
high or too low. 

10. ABOUT SOFT START TECHNOLOGY

This inverter has advanced soft start function. The output voltage rises up  from low to 
normal when the inverter is turned on. 
1.This  can  reduce  high  startup  currents,  which  can  make  startup  easier  for  large 

inductive loads.   

2.As for the large inductive loads, such as electric tools and capacitive loads, 
We  suggest  turning  on  the  switch  of  the  appliance  firstly  and  then  the  inverter's.  The 

soft start .May be enough to power the high staring.

11. LED DISPLAY:

When  the  product  is  working,  the  LED  display  will  alternately  display  the  input 

voltage and the output the current state of protections:
1. Input(V) LED is on, digital display is the value of the input voltage
2. Output(KW) LED is on, digital display is the value of the output power
3. Output(W) LED is on, digital display is the value of output power 
4. Display LO, indicates the current status of under voltage protection
5. Display shows HI, indicates the current status of over voltage protection
6.  Display  shows  OL,  indicates  the  current  status  of  output  overload  or  short-circuit 

protection

7.Display shows OH,  indicates the current status of overheat protection.

12. PROTECTION FEATURES:

1. Input under-voltage alarm: When the input DC voltage is lower than 10.1V(20.2V), the 

buzzer  will  whistle  intermittently  to  remind  that  the  inverter  will  go  into  the  under 
voltage protection. Pay attention to save the data if you are using computer. 

2.  Under  voltage  protection:  The  inverter  will  automatically  shut  down  when  the  input 

DC  voltage  is  lower  than  9.8V(19.6V).The  buzzer  will  whistle  continuously  and  the 
green  light  is  off,  red  light  is  on.  Please  turn  off  the  inverter  and  use  it  after 
recharging the battery.  

3. Over voltage protection: The inverter will automatically shut down when the input DC 

voltage is higher than 16V(32V).The buzzer will whistle continuously and the green 
light is off, red light is on. Please turn off the inverter and adjust the input voltage to 
the admissible range.

4.  Overload  protection:  The  inverter  will  automatically  shut  down  when  the  load  is 

higher  than  the  rated  power.  The  buzzer  will  whistle  continuously.  Turn  off  the 
inverter and resume to normal operation after taking away the excessive load.

5.  Short-circuit  protection:  The  AC  output  will  be  automatically  shut  down  when  short 

circuited. It will automatically reset after the problem is solved.

6.  Thermal  protection:  The  unit  will  get  bot  during  operation.  If  the  temperature  is 

higher  than  149°F,  the  inverter  will  automatically  shut  down.  Then  the  buzzer  will 
whistle  continuously  and  the  green  light  is  off,  red  light  is  on.  Please  turn  off  the 
inverter, and continue using it after the temperature goes back to normal naturally. 
Meanwhile  find  out  the  factors  causing  the  fault,  such  as  ventilation,  ambient 
temperature, vent, load power and so on. It can avoid similar things from happening 
again.