6.5.6 Bargraph Display
The bargraph display is a compact process display used to visualize the flow value in
the range from 0 to 100% with a 16-segment display. The bar graph displays the cur-
rent flow (segments 0 to 16 represent the range between flow standstill and maximum
flow).
NOTE
If a selected flow unit requires a numerical value greater than 9999, an error message
is displayed. If necessary, the decimal places are reduced automatically.
6.5.7 "Decimals" parameter
Sets the number of decimal places for "Max flow rate".
Setting values:
0,
No decimal place
0,0
One decimal place
0,00
Two decimal places
0,000
Three decimal places
variable
Depending on the display value (max. 4 digits), the decimal
point can shift automatically. For display values from 0 to
9.999, three decimal places are used; for display values from
10.00 to 99.99, two decimal places are used; for display val-
ues 100.0 to 999.9, one decimal place is used. Display va-
lues from 1000 to 9999 are displayed without decimal places.
NOTE
With fixed setting of e.g. 2 decimal places and the display value is up to 999, the dis-
play is automatically switched to 1 decimal place, for display values above 1000 no
decimal place is displayed.
6.5.8 "Max flow rate" parameter
"Max flow rate" is the maximum measurable flow rate. The value is calculated from the
"Max velocity" and "Pipe diameter" parameters and is only for the user's information. It
cannot be edited directly and therefore has no setting range. It is displayed in the unit
set under "Unit" with the number of decimal places set under "Decimals".
Display value: 4 digits with the decimal number set in "Decimals
Содержание HONSBERG OMNIPLUS-F Series
Страница 1: ...Operating manual OMNIPLUS F Thermal flow sensor EN ...
Страница 21: ...OMNIPLUS F Operation 6 C E01_X__OMNIPLUS F__DB2 1 0 21 45 Overview of the parameters of the submenus ...
Страница 22: ...6 Operation OMNIPLUS F 22 45 C E01_X__OMNIPLUS F__DB2 1 0 ...
Страница 23: ...OMNIPLUS F Operation 6 C E01_X__OMNIPLUS F__DB2 1 0 23 45 ...