Part No.: 790 000
GfS Door Teminal
5
790000_Ai_GfS-Door_Terminal_1112_GB
TERMINAL DIAGRAM
Pos
Abb.
Function
Signal
1
GND
Operating voltage minus
Ground
2
+24V
Operating voltage plus
+24 V
3
FACS
Fire alarm control system
Floating contact or bridge to 4
4
FACS
Fire alarm control system
Floating contact or bridge to 3
5
NO1
Response magnet 1
Ground is switched, holding magnet 1 is energized (Hall Relay NO)
6
NO2
Response magnet 2
Ground is switched, holding magnet 2 is energized (Hall Relay NO).
In case that there is just 1 magnet, 6 and 7 must be bridged!
7
GND
Common GND Magnets
GND-Signal (Hall Relais COM)
8
Magnet-
Magnet- Coil 1 and 2
Negative connection for magnets
9
Coil 1 and 2
Positive connection for magnets
10
GND
Reference for remote opening
Signal ground
11
REM
Remote opening input Switch-on
GND resp. bridge 10 and 11 Opening command
12
GND
Reference contact for door contact
Signal GND
13
DC
Contact
Switch-on GND resp. bridge 12 and 13. Door closed
14
RS-485A
Communication
Data signals
15
RS-485B
Communication
Data signals
16
DST
Communication multi function port
Acc. to the required functions as input or output, also usable for communication
purposes with 1 wire
17
COM
Incident message relay COM
Floating contact 30 V/0,5 A max
18
NC
Incident message relay NC
Floating contact 30 V/0,5 A max
19
NO
Incident message relay
Floating contact 30 V/0,5 A max
20
ext. flash
External flash light
Open collector-output, 30V/ 0,5A max
21
ext. sir.
External siren
Open collector-output, 30V/ 0,5A max
22
GND
Reference for reserve and dim input Signal GND
23
Res1
Reserve input
Free function
24
Dim
Dim input
Switch-on GND resp. bridge 24 with 22. Dim command
1
GND
2
+ 24 V
3
FACS
4
FACS
5
NO 1
6
NO 2
7
GND
8
Mag –
9
Mag +
20
Dim
21
Res 1
22
GND
23
ext. sir.
24
ext. flash
10
GND
11
REM
12
GND
13
DC
14
RS485-A
15
RS485-B
16
DST
17
COM
18
NC
19
NO
12 V – 24 V
+