After exiting programming, the door must carry out a full OPEN and CLOSE-operation in self-
hold mode.
The force monitoring is a self-learning system which is effective for an opening gap of 5 cm to
2 m (approx.). Slow progressive changes, e.g. gradual reduction of the spring torsion, are
compensated automatically.
After force monitoring has been triggered, only the "Hold-to-run" door operating mode is
possible and the F4.1 fault indication is displayed. The resetting occurs when a final limit
position for the door is reached.
Travel time monitoring (NES only)
Menu item 3.3
The set travel time is automatically compared with the time measured for movement between
the final limit positions. If the travel time is exceeded, the F5.6 fault indication appears.
Fault indication F5.6 is reset by closing the door.
Note!
The travel time is set at the factory to 90 seconds
Recommended setting value: door travel time + 7 seconds