6
2
Technical data of the drive unit
Explosion protection
II 2G Ex db eb h IIC T4 Gb
II 2D Ex tb h IIIC 130°C Db
Output torque
400
Nm
Output speed
24
rpm
Output / hollow shaft
40,00
mm
Maximum output speed Open / Close
for frequency inverter operation
24
rpm
Supply voltage
3~ 400
V
Operating current
2,70
A
Operating frequency
50
Hz
Power factor cos
φ
0,76
Maximum movements per hour
12
h
-1
Manual force, emergency manual operation
246
N
Protection class
IP 65
Limit switch range
(maximum revolutions of the output / hollow shaft)
20
Temperature range
-20 / +40
°C
Installation height
< 1000
m
Components used
Gearbox
SG 85 60.T4
Motor
F80-2GD CTVF /4
Terminal box
8146/1041
Limit switch / emergency manual operation switch
07-2511