8350-3 Temperature Transmitter Instructions

Menu Functions

Troubleshooting

Display

+ -- -- --
-- -- -- --
Check Sensor ?

Value must be
400 or less

Process in bounds
Relay always activated
Relay annunciation

SETUP READ ERROR
Press Any Key

Problem

Over or under range

No sensor detected
You may enter the CALIBRATION and
OPTIONS menu to program setpoint values
even though Check Sensor? is displayed.

Output PULSE mode selected,
max pulse rate greater than 400.

Hysteresis set too large.

Memory fault occurred.

Solution

Verify

Connect sensor
Turn power off then back on to recognize sensor

Select a pulse rate equal to or less than 400

Re-enter smaller hysteresis value.

Press any key to reload presets, then reprogram
setpoints.

View Menu

Range

Calibrate Menu

Range

Preset

Options Menu

Range

Preset

Temp1: Temp

-10- 100 °C

Switch  ID:

Sensor1 to 2

Random

Contrast:

1-5

3

Temp2: Temp

(14 - 212 °F)

>

Sensor2 to 1

Level    >

Delta Temp:

± 110 °C

Temp Units:

°C

°C   

Averaging:

Off

Off

Temp1-Temp2

(± 198 °F)

°C        > 

°F

Off      >

Low (4secs)

Loop1  Output:

4-20 mA

Set:

± 20°C

N/A

High(8secs)

mA

Temperature  >

Output1  Active:

Low

Low

Loop2  Output:

4-20 mA

Loop1 Source:

Temp1

Temp1

Low       >

High

mA

Temp1  >

Temp2

Output2  Active:

Low

Low

Last  Cal:

00-00-00 to

DT (1-2)

Low       >

High

Date

39-39-99

Loop1 Range: °C

-10 - 100°C

0 - 100°C

Loop1  Adjust:

3.8  to

4.00

0.0 > 100.0  >

14 - 212°F

      4.00 mA    >

5.0 mA

 mA

(4mA)  (20 mA) 

±199 (DT)

Loop 1 Adjust:

19.0 to 

20.00

Loop2 Source:

Temp1

Temp2

       20.00 mA   >

21.0 mA

 mA

Temp2  >

Temp2

Loop2  Adjust:

3.8  to

4

DT (1-2)

      4.00 mA    >

5.0 mA

 mA

Loop2 Range: °C

-10 - 100°C

0 - 100°C

Loop 2 Adjust:

19.0 to 

20

0.0 > 100.0  >

14 - 212°F

       20.00 mA   >

21.0 mA

 mA

(4mA)  (20 mA) 

±199 (DT)

Test Loop1:

4-20 mA

N/A

>

Output1  Source:

Temp1

Temp1 (Output1)

Test Loop2:

4-20 mA

N/A

Temp1  >

Temp2

Temp2 (Output2)

>

DT (1-2)

Test  Output1:

On or

N/A

Output1 Mode:

Off

Low (Output1)

>

Off

Low        >  

Low

Hi (Output2)

Test  Output2:

On or

N/A

Hi

>

Off

Pulse

Low or High Selected

Output1  Setpnt:

-10 - 100 °C

25 °C (Output1)

Settings repeat for Output2

25 °C    >   

(14 - 212 °F)

45 °C (Output2)

Output1  Hys:

0 - 999.9

1 °C

1 °C    >

Pulse Selected

Output1 Range:

-10 - 100 °C

25->45 °C

25.0 -> 45.0   >

(14 - 212 °F)

45->80 °C

(Start>Endpoint)

Output1  PlsRate:

0-400

120

120 pulses/min >

pulses/min

pulses/min

Last  Cal:

00-00-00 to 

01-01-99

01-01-99     >

39-39-99

Содержание SIGNET 8350-3

Страница 1: ...rsal Assembly 3 8050 1 Install transmitter base 2 Connect wires to transmitter 3 Close unit and secure with push and twist lock Seal cable entry 1 Installation The transmitter is available in three ve...

Страница 2: ...5 Red Sensr 2 IN 16 Silver Sensr 2 Gnd Wiring Tips Do not route sensor cable in conduit containing AC power wiring electrical noise may interfere with sensor signal Routing sensor cabling in grounded...

Страница 3: ...upply DC 12 24 V Power Supply Power Supply Connection to a PLC with built in power supply PLC Terminals Power Supply Ground Power Supply Channel 2 4 20 mA in Channel 2 4 20 mA in Channel 1 4 20 mA in...

Страница 4: ...CAL 08 01 99 LAST CAL 01 01 99 GF SIGNET LAST CAL 01 01 99 Example To change date first enter CALIBRATE menu Press ENTER button for 2 seconds Press UP UP UP DOWN buttons in sequence Once in CALIBRATE...

Страница 5: ...Low 4secs Loop1 Output 4 20 mA Set 20 C N A High 8secs mA Temperature Output1 Active Low Low Loop2 Output 4 20 mA Loop1 Source Temp1 Temp1 Low High mA Temp1 Temp2 Output2 Active Low Low Last Cal 00 00...

Страница 6: ...page 6 of 8 8350 3 Temperature Transmitter Instructions...

Страница 7: ...page 7 of 8 8350 3 Temperature Transmitter Instructions...

Страница 8: ...1 Aerojet Avenue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website gfsignet com Or call in the U S 800 854 4090 GEORGE FISCHER GF Piping...

Отзывы: