8350-3 Temperature Transmitter Instructions

3.1  System Power/Loop Connections

3.2

Sensor Input Connections

Wiring Tip:
Do not route sensor cable in any conduit
containing AC power wiring - electrical
noise may interfere with the signal.

Off:

  Disables output pulse.

Proportional Pulse Mode Operation

The output emits a 100 mS pulse (simulated contact closure) at
rate defined by the Output, Pulse Range, Output Rate, and the
process condition  (0 to 400 pulses/minute, as programmed)

Example:  As the process falls below 10 the output will start
pulsing in relation to the process value, the max pulse endpoint
and the programmed pulses/min.  Pulse rate will increase as
the process approaches the programmed endpoint.

3.3  Open Collector Functions

Low:

  Output triggers when process variable is less than

setpoint.

High:

  Output triggers when process variable is higher than

setpoint.

Example:  In Low Alarm Mode Operation, the output becomes
active when the process drops below the setpoint, and
becomes inactive when the process rises above the setpoint
plus hysteresis.  The opposite is true for High Alarm Mode.

Stand-alone application, no current loop used

Transmitter

           Terminals

6
5
4
3
2
1

Loop2-

Loop2+

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Power Supply
DC 12 - 24 V

Power
Supply
Power
Supply


+

Connection to a PLC with built-in power supply

PLC

Terminals

Power Supply
Ground
Power
Supply
Channel 2
4-20 mA in
Channel 2
4-20 mA in
Channel 1
4-20 mA in
Channel 1
4-20 mA in






+

Internal PLC
Connection

NC
NC

Connection to a PLC/Recorder, separate supply

PLC or Recorder

Channel 2
4-20 mA in
Channel 2
4-20 mA in
Channel 1
4-20 mA in
Channel 1
4-20 mA in




+

DC 12 - 24 V

Power
Supply
Power
Supply


+

PLC or Recorder

-       Channel 4
+      Channel 4
-       Channel 3
+      Channel 3
-       Channel 2
+      Channel 2
-       Channel 1
+      Channel 1
  

DC 12 - 24 V

Power
Supply
Power
Supply


+

Transmitter

           Terminals

6
5
4
3
2
1

Loop2-

Loop2+

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

Transmitter

           Terminals

6
5
4
3
2
1

Loop2-

Loop2+

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

6
5
4
3
2
1

Loop2-

Loop2+

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

6
5
4
3
2
1

Loop2-

Loop2+

Sys. Pwr.
Loop -
Sys. Pwr.
Loop +
AUX
Power -
AUX
Power +

T

ransmitter 1                        

T

ransmitter 2

Example:  Two transmitters connected to PLC/Recorder

with separate power supply

Silver (Snsr 2 Gnd)
Red (Snsr 2 IN)
Black (Snsr 2 V+)
Silver (Snsr 1 Gnd)
Red (Snsr 1 IN)
Black (Snsr 1 V+)

16
15
14
13
12
11

+GF+ SIGNET 2350

Temperature Sensors

Terminals

Hysteresis

Output active

Output inactive

Time

Setpoint

Process

Relay 1 
or Relay 2

10

5

Relay 1: Pulse

10.0000

5.0000>

Output1 Rate:

100 Pulses/min>

I 10I =I

1I pulses/min.

I7.5I =I 50I pulses/min.
I 5I =I 100I pulses/min.

Start

max. pulse endpoint

Pulse rate

Process variable

0 pulses

100 pulses

Содержание SIGNET 8350-3

Страница 1: ...rsal Assembly 3 8050 1 Install transmitter base 2 Connect wires to transmitter 3 Close unit and secure with push and twist lock Seal cable entry 1 Installation The transmitter is available in three ve...

Страница 2: ...5 Red Sensr 2 IN 16 Silver Sensr 2 Gnd Wiring Tips Do not route sensor cable in conduit containing AC power wiring electrical noise may interfere with sensor signal Routing sensor cabling in grounded...

Страница 3: ...upply DC 12 24 V Power Supply Power Supply Connection to a PLC with built in power supply PLC Terminals Power Supply Ground Power Supply Channel 2 4 20 mA in Channel 2 4 20 mA in Channel 1 4 20 mA in...

Страница 4: ...CAL 08 01 99 LAST CAL 01 01 99 GF SIGNET LAST CAL 01 01 99 Example To change date first enter CALIBRATE menu Press ENTER button for 2 seconds Press UP UP UP DOWN buttons in sequence Once in CALIBRATE...

Страница 5: ...Low 4secs Loop1 Output 4 20 mA Set 20 C N A High 8secs mA Temperature Output1 Active Low Low Loop2 Output 4 20 mA Loop1 Source Temp1 Temp1 Low High mA Temp1 Temp2 Output2 Active Low Low Last Cal 00 00...

Страница 6: ...page 6 of 8 8350 3 Temperature Transmitter Instructions...

Страница 7: ...page 7 of 8 8350 3 Temperature Transmitter Instructions...

Страница 8: ...1 Aerojet Avenue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website gfsignet com Or call in the U S 800 854 4090 GEORGE FISCHER GF Piping...

Отзывы: