8350-3 Temperature Transmitter Instructions

4. Menu Functions

VIEW Menu:

  is displayed during standard operation.

Press UP or DOWN buttons to view process parameters.

Press UP and DOWN buttons at the same time, to exit any
other display and return to VIEW menu.

Display will return to VIEW menu in 10 minutes unless a key
is pressed.

CALIBRATE Menu:  

contains display setup and output

parameters.  A  security code feature prevents unauthorized
tampering.  To access CALIBRATE menu:

Press ENTER button for 2 seconds to display:

Press UP, UP, UP, DOWN buttons in sequence
to display:

OPTIONS Menu:  

contains setup and display features for minor

display or output adjustments.  To access OPTIONS menu:

Press ENTER button for 5 seconds to display:

Press UP, UP, UP, DOWN buttons in sequence
to display:

Menu Tips

Right button scrolls to right, from top to bottom row, and allows
editing when  ">" symbol is shown.

In CALIBRATE or OPTIONS menus, the transmitter will
continue to measure and control outputs.  When > is pressed,
the input value is held at the last measured process value.

When sensor is not connected, unit will display CHECK
SENSOR and any output controlled by sensor will be at 3.6 mA
or OFF.

LAST CAL:

08-01-99

LAST CAL:

01-01-99

+GF+ SIGNET

LAST CAL:

01-01-99   >

Example

To change date, first enter CALIBRATE menu  (Press ENTER button for 2 seconds;  Press UP, UP, UP, DOWN buttons in sequence)  
Once in CALIBRATE menu, press UP button 1 time.

SAVING

ENTER

1.

I Display shows right 

I

arrow 

3.

I Press buttons to scroll

I

through numbers.

2.

I Press RIGHT button 

I

to display "01" blinking

4.

I Press ENTER button

I

to save

5.

I Display now reads 

I

new date

ENTER

LAST CAL:

08-01-99

ENTER

ENTER

+GF+ SIGNET

ENTER

+GF+ SIGNET

+GF+ SIGNET

+GF+ SIGNET

CALIBRATE: ----
 Enter Key Code

CALIBRATE: XXXX
 Enter Key Code

OPTIONS: ----

 Enter Key Code

OPTIONS: XXXX

 Enter Key Code

3.4  Differential Mode (2 Sensor Inputs Required)

The selected open-collector or current output is based on the
difference of Sensor 1 minus Sensor 2.  To enable differential
mode, the selected output's "Source" selection must be set to
differential mode "DF", "DT", or "DP".

Sensor 1 - Sensor 2 = Difference

1. Unit of measure is based on Sensor 1.
2. Decimal is based on Sensor 2.  Sensor 2 should be the

smallest unit measured or negative values will be generated.

3. Difference calculated in units only;  not percentage.

+GF+ SIGNET

ENTER

Sensor 1 (80)

Sensor 2 (20)

For pressure and temperature transmitters ensure Sensor 1 is
equal to ID 1:

Sensor 1 - Sensor 2
Difference = 60

Example:  4-20 mA
Loop1 Range:  0-120
Loop1: = 12.00 mA

Example:  Output
Output1 Mode:  Low
Output1 Setpoint:  70
Output1 = ON

Содержание SIGNET 8350-3

Страница 1: ...rsal Assembly 3 8050 1 Install transmitter base 2 Connect wires to transmitter 3 Close unit and secure with push and twist lock Seal cable entry 1 Installation The transmitter is available in three ve...

Страница 2: ...5 Red Sensr 2 IN 16 Silver Sensr 2 Gnd Wiring Tips Do not route sensor cable in conduit containing AC power wiring electrical noise may interfere with sensor signal Routing sensor cabling in grounded...

Страница 3: ...upply DC 12 24 V Power Supply Power Supply Connection to a PLC with built in power supply PLC Terminals Power Supply Ground Power Supply Channel 2 4 20 mA in Channel 2 4 20 mA in Channel 1 4 20 mA in...

Страница 4: ...CAL 08 01 99 LAST CAL 01 01 99 GF SIGNET LAST CAL 01 01 99 Example To change date first enter CALIBRATE menu Press ENTER button for 2 seconds Press UP UP UP DOWN buttons in sequence Once in CALIBRATE...

Страница 5: ...Low 4secs Loop1 Output 4 20 mA Set 20 C N A High 8secs mA Temperature Output1 Active Low Low Loop2 Output 4 20 mA Loop1 Source Temp1 Temp1 Low High mA Temp1 Temp2 Output2 Active Low Low Last Cal 00 00...

Страница 6: ...page 6 of 8 8350 3 Temperature Transmitter Instructions...

Страница 7: ...page 7 of 8 8350 3 Temperature Transmitter Instructions...

Страница 8: ...1 Aerojet Avenue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website gfsignet com Or call in the U S 800 854 4090 GEORGE FISCHER GF Piping...

Отзывы: