Pg 1 of 12
‡ SIGNET
5900 Salinity Monitor
‡ SIGNET 5900 Salinity Monitor
ENGLISH
3.
4-20 mA Current Output Connections
CAUTION!
•
Refer to instruction manual for more details.
•
Remove power to unit before wiring input and output
connections.
•
Follow instructions carefully to avoid personal injury.
1.
Power Connections
2.
Compatible Sensor Wiring
Technical Notes:
•
To reduce the possibility of noise interference, isolate AC
power lines from signal lines.
•
Maximum 4-20 mA loop impedance is affected by the supply
voltage.
Technical Notes:
•
Use three conductor shielded cable for cable extensions up to
30 m (100 ft) max.
•
Cable shield MUST be maintained through cable splice.
Contents
1.
Power Connections
2.
Compatible Sensor Wiring
3.
4 - 20 mA Current Output Connections
4.
Relay Connections
5.
Relay Operation
6.
Menu Functions
CAUTION!
Never connect 110 VAC or 220 VAC
to rear power
terminals. High voltage AC will damage instrument and
void warranty.
Technical Notes:
** 1/8A fuse recommended (customer supplied)
*
4-20 mA output is
internally powered
(non-isolated),
maximum loop impedance 350
Ω
with a 12 V instrument
supply voltage, 950
Ω
with a 24 V instrument supply voltage.
To isolate output and prevent ground loop problems:
1.
Use monitor device with isolated inputs, or
2.
Use separate DC supply for 5900 and monitor device, or
3.
Power 5900 with 12 - 24 VAC step down transformer
12-24 V
10 W
-
+
12 - 24 VDC
OR
12 - 24 VAC
5900 Terminals
External power supply
= Double Insulated
= DC or AC power
-
+
Signal IN
Temp. IN
Iso. Gnd
Shld
Silver (Shld)
Black
White
Red
+GF+ SIGNET Sensor
Range (PPT):
3-2822-1 (10.0)
0 - 80
3-2823-1 (20.0)
PPT
20.0
10.0
5900
Terminals
-
+
4-20
mA
-
+
Fuse**
1/8A
4 - 20 mA*
*
5900 Terminals
3-5900.090-1
C (6/01) English
7.
Temperature Coefficient
8.
Parts and Accessories
9.
Specifications
10.
Quick Reference Menu Parameters
11.
Troubleshooting
12.
Maintenance
Total
reset
AUX
output
PLS
output
1
2
Gnd
+
+
-
+
Gnd
Freq. IN
Sen. Pwr.
Freq. IN
Iso. Gnd
Std. Sensor
Patent No. D376,328
Flow
Open Collector
Sensor
12-24 V
10 W
LISTED
77CJ
UL
1 2 3 4 5 6
1 2 3 4
1 2
1 2
Total
reset
AUX
output
PLS
output
1
2
Gnd
+
+
-
+
Gnd
Freq. IN
Sen. Pwr.
Freq. IN
Iso. Gnd
Std. Sensor
Patent No. D376,328
Flow
Open Collector
Sensor
12-24 V
10 W
LISTED
77CJ
UL
1 2 3 4 5 6
1 2 3 4
1 2
1.
2.
3.
Remove terminal blocks for easy wiring
Содержание SIGNET 5900
Страница 11: ...Pg 11 of 12 SIGNET 5900 Salinity Monitor...