background image

Pg 7 of 12

‡ SIGNET 

5900 Salinity Monitor

9.  Specifications

General

Compatible sensors: +GF+ SIGNET 3-28XX-1 Standard and

Certified Series Sensors

Accuracy:

±

0.5% PPT

Input range:

1 to 80 PPT optically isolated

Enclosure:
• NEMA 4X/IP65 front
• Dimensions:  1/4 DIN, 96 x 96 x 88 mm (3.8 x 3.8 x 3.5 in.)
• Case materials:  ABS plastic
• Keypad material:  Sealed 4-key silicone rubber
• Weight:  500 g  (18 oz.)

Display:
• Type:  Microprocessor controlled air-core meter movement and

backlit alphanumeric 2 x 16 LCD

• Update rate:  <2s
• Contrast:  User selected
• Relay annunciators:  2 LEDs
• Displayed units:  PPT (Salinity), 

µ

S, mS, k

, M

, PPM (TDS)

Environmental

Operating temp.:

-10  to 55

°

C (14 to 131

°

F), 50

°

C (122

°

F) max.

with optional rear cover

Storage temp.:

-15 to 80

°

C (5 to 176

°

F)

Relative humidity:

0 to 95%, non-condensing

Altitude:

4000 m max.

Pollution degree:

2

Electrical

Power requirements:
• 12 to 24 VDC or 12 to 24 VAC, unregulated, 50-60 Hz,

10 W max.

Temperature input:
• PT1000, 0 to 100

°

C (32 to 212

°

F), optically isolated

Dimensions

:

Relay outputs (2 sets):
• Mechanical SPDT contacts
• Max. voltage rating: 5 A @ 30 VDC, 5 A @ 125 VAC, or

3 A @ 250 VAC, (power factor = 1.0)

• Hysteresis: User adjustable

Current output:
• 4 to 20 mA, non-isolated, internally powered, fully adjustable and

reversible

• Update rate: <2s
• Max loop impedance: 350 

 with a 12 V instrument supply

voltage, 950 

 with a 24 V instrument supply voltage

• Accuracy 

±

0.1% of max range

Noise immunity:

EN50082-2

Noise emissions:

EN55011

Safety:

EN61010-1

Agency Approvals
• CSA, CE, UL listed
• Manufactured under ISO 9001

88 mm
(3.5 in.)

88 mm (3.5 in.)

Mounting Clamp

Optional
Splashproof 
Rear Cover

88 mm
(3.5 in.)

Mounting Panel

Panel Gasket

91 mm
(3.6 in.)

76 mm (3 in.)

96 mm (3.8 in.)
88 mm (3.5 in.)

Front View

Panel Cutout

92 x 92 mm

(3.62 x 3.62 in.)

Rear View

Side View

96 mm
(3.8 in.)

96 mm (3.8 in.)

Relay 2

Relay 1

ENTER

0

2

4

6

8

10

ppt

62.50 PPT

+25.0  

°

C

4-20 

mA

-

+

NC

C

NO

NC

C

NO

-

+

Relay 1

Relay 2

12-24 V

10 W

 Patent No. D 376,328

     

 Patent No. 5,708,363       

Salinity

+GF+ SIGNET
Model #3-5900

®

LISTED
77CJ

UL

®

Signal IN

Red wire

Iso. Gnd

Black wire

Shld

Silver wire

Temp. IN

White wire

0.055      1       10    100    200     1,000    10,000            200,000    400,000
(18 M

)                (10 k

)

2819-1

2823-1

Conductivity Range (

µ

S)

+GF+ SIGNET Conductivity Sensor Ranges 

Sensor Models

Ultra-

Pure   Pure  Rinse

2821-1

2822-1

2820-1

Salinity Range

Содержание SIGNET 5900

Страница 1: ...ered non isolated maximum loop impedance 350 with a 12 V instrument supply voltage 950 with a 24 V instrument supply voltage To isolate output and prevent ground loop problems 1 Use monitor device wit...

Страница 2: ...ents or operating currents that exceed the above specifications 5 2 HIGH alarm mode The relay is active when the solution salinity PPT rises above the setpoint and is inactive when the solution salini...

Страница 3: ...0 100 See dial kit for additional information 6 1 VIEW Menu Menu Displays A G Factory default displays shown in menu column 1 A Active display of salinity PPT and temperature in degrees celsius C or f...

Страница 4: ...int 00 0000 999999 units G Sets relay hysteresis 00 0000 999999 units Set to zero to disable feature H Sets relay minimum and maximum pulse setpoint 00 0000 999999 units I Sets relay pulse rate 000 30...

Страница 5: ...any test solution for calibration purposes The 2 step WET CAL process first allows for verification or calibration of temperature followed by verification or calibration of salinity PPT using a known...

Страница 6: ...A Adjust 3 88 mA Low High ENTER SAVING displayed A B C D E F Contrast 3 Display Decimal Display Average Low Set 4 mA 0 0000 PPT Set 20 mA 40 000 PPT 4 mA Adjust 4 00 mA 4 mA Adjust 4 00 mA Display Dec...

Страница 7: ...acts Max voltage rating 5 A 30 VDC 5 A 125 VAC or 3 A 250 VAC power factor 1 0 Hysteresis User adjustable Current output 4 to 20 mA non isolated internally powered fully adjustable and reversible Upda...

Страница 8: ...40 0000 WET CAL Relay 1 Low 10 0000 PPT Relay 1 Hys 4 0000 Relay 1 Pulse 10 0000 30 0000 Relay 1 Rate 120 Pulses min Last CAL 01 01 98 Sensor type and cell constant Process Units Min Max meter dial r...

Страница 9: ...age 0 5 Off 0 sec Low 4 sec High 8 sec 00 0000 999999 00 0000 999999 3 0 5 0 mA 19 21 mA Celsius or Fahrenheit 0 00 9 99 3 Low 4 sec 00 0000 PPT 40 0000 PPT 4 00 mA 20 00 mA C 2 00 A B C D E F G H I M...

Страница 10: ...fy sensor wiring B Verify instrument temperature input Remove Black and White sensor wires from rear Temp IN and Iso Gnd terminals then place a 1100 resistor across terminals Power instrument and veri...

Страница 11: ...Pg 11 of 12 SIGNET 5900 Salinity Monitor...

Страница 12: ...nue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website www gfsignet com Or call in the U S 800 854 4090 GEORGE FISCHER Piping Systems 3 59...

Отзывы: