5900 Salinity Monitor

‡ SIGNET 5900 Salinity Monitor

ENGLISH

3.

4-20 mA Current Output Connections

CAUTION!

Refer to instruction manual for more details.

Remove power to unit before wiring input and output
connections.

Follow instructions carefully to avoid personal injury.

1.

Power Connections

2.

Compatible Sensor Wiring

Technical Notes:

To reduce the possibility of noise interference, isolate AC
power lines from signal lines.

Maximum 4-20 mA loop impedance is affected by the supply
voltage.

Technical Notes:

Use three conductor shielded cable for cable extensions up to
30 m (100 ft) max.

Cable shield MUST be maintained through cable splice.

Contents

1.

Power Connections

2.

Compatible Sensor Wiring

3.

4 - 20 mA Current Output Connections

4.

Relay Connections

5.

Relay Operation

6.

Menu Functions

CAUTION!
Never connect 110 VAC or 220 VAC

 to rear power

terminals.  High voltage AC will damage instrument and
void warranty.

Technical Notes:

** 1/8A fuse recommended (customer supplied)
*

4-20 mA output is 

internally powered

 (non-isolated),

maximum loop impedance 350 

 with a 12 V instrument

supply voltage, 950 

 with a 24 V instrument supply voltage.

To isolate output and prevent ground loop problems:

1.

Use monitor device with isolated inputs, or

2.

Use separate DC supply for 5900 and monitor device, or

3.

Power 5900 with 12 - 24 VAC step down transformer

12-24 V

10 W

-

+

12 - 24 VDC

OR

12 - 24 VAC

5900 Terminals

External power supply

= Double Insulated

= DC or AC power

-

+

Signal IN

Temp. IN

Iso. Gnd

Shld

Silver (Shld)

Black

White

Red

+GF+ SIGNET Sensor

Range (PPT): 

3-2822-1 (10.0)

0 - 80

3-2823-1 (20.0)

PPT

20.0

10.0

5900
Terminals

-

+

4-20 

mA

-

+

Fuse**

1/8A

4 - 20 mA*

*

5900 Terminals

3-5900.090-1

C (6/01) English

7.

Temperature Coefficient

8.

Parts and Accessories

9.

Specifications

10.

Quick Reference Menu Parameters

11.

Troubleshooting

12.

Maintenance

Total
reset

AUX

output

PLS

output

1

2

Gnd

+

+

-

+

Gnd

Freq. IN

Sen. Pwr.

Freq. IN

Iso. Gnd

Std. Sensor

        

  Patent No.  D376,328

     Flow

Open Collector 
Sensor

12-24 V

10 W

LISTED
77CJ

UL

 1   2   3   4   5   6

 1   2   3   4

 1   2

 1   2

Total
reset

AUX

output

PLS

output

1

2

Gnd

+

+

-

+

Gnd

Freq. IN

Sen. Pwr.

Freq. IN

Iso. Gnd

Std. Sensor

        

  Patent No.  D376,328

     Flow

Open Collector 
Sensor

12-24 V

10 W

LISTED
77CJ

UL

 1   2   3   4   5   6

 1   2   3   4

 1   2

1.

2.

3.

Remove terminal blocks for easy wiring

Содержание SIGNET 5900

Страница 1: ...ered non isolated maximum loop impedance 350 with a 12 V instrument supply voltage 950 with a 24 V instrument supply voltage To isolate output and prevent ground loop problems 1 Use monitor device wit...

Страница 2: ...ents or operating currents that exceed the above specifications 5 2 HIGH alarm mode The relay is active when the solution salinity PPT rises above the setpoint and is inactive when the solution salini...

Страница 3: ...0 100 See dial kit for additional information 6 1 VIEW Menu Menu Displays A G Factory default displays shown in menu column 1 A Active display of salinity PPT and temperature in degrees celsius C or f...

Страница 4: ...int 00 0000 999999 units G Sets relay hysteresis 00 0000 999999 units Set to zero to disable feature H Sets relay minimum and maximum pulse setpoint 00 0000 999999 units I Sets relay pulse rate 000 30...

Страница 5: ...any test solution for calibration purposes The 2 step WET CAL process first allows for verification or calibration of temperature followed by verification or calibration of salinity PPT using a known...

Страница 6: ...A Adjust 3 88 mA Low High ENTER SAVING displayed A B C D E F Contrast 3 Display Decimal Display Average Low Set 4 mA 0 0000 PPT Set 20 mA 40 000 PPT 4 mA Adjust 4 00 mA 4 mA Adjust 4 00 mA Display Dec...

Страница 7: ...acts Max voltage rating 5 A 30 VDC 5 A 125 VAC or 3 A 250 VAC power factor 1 0 Hysteresis User adjustable Current output 4 to 20 mA non isolated internally powered fully adjustable and reversible Upda...

Страница 8: ...40 0000 WET CAL Relay 1 Low 10 0000 PPT Relay 1 Hys 4 0000 Relay 1 Pulse 10 0000 30 0000 Relay 1 Rate 120 Pulses min Last CAL 01 01 98 Sensor type and cell constant Process Units Min Max meter dial r...

Страница 9: ...age 0 5 Off 0 sec Low 4 sec High 8 sec 00 0000 999999 00 0000 999999 3 0 5 0 mA 19 21 mA Celsius or Fahrenheit 0 00 9 99 3 Low 4 sec 00 0000 PPT 40 0000 PPT 4 00 mA 20 00 mA C 2 00 A B C D E F G H I M...

Страница 10: ...fy sensor wiring B Verify instrument temperature input Remove Black and White sensor wires from rear Temp IN and Iso Gnd terminals then place a 1100 resistor across terminals Power instrument and veri...

Страница 11: ...Pg 11 of 12 SIGNET 5900 Salinity Monitor...

Страница 12: ...nue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website www gfsignet com Or call in the U S 800 854 4090 GEORGE FISCHER Piping Systems 3 59...