Problem
Possible causes
Remedy
Motor does not run
no mains voltage available
error at customer side
(terminals 1,2,3)
internal wiring error
check wiring of actuator
switching cams S1 and S2
see point 6
set incorrectly
motor blocked
use emergency manual override,
check the valve
Motor only runs in
limit switch defective
replace limit switch
one direction
Overload protection reacts
torque of valve too high
clean and lubricate valve
(self-resetting)
duty cycle too high
increase cycle time
reduce ambient temperature
Valve does not close or
switching cams S1 and/or S2
see point 6
open correctly
not adjustedt
8. TROUBLESHOOTING
For service please contact the specialist at your Georg Fischer sales company.
In case an end position is not reached, the actuator shuts off automatically after
2 minutes and reports error message.