57
Cycle time extension (Vario)
Description
Technical data
Code
Cycle time extension
199 190 080
The cycle time extension increases the cycle time of the
electric actuator. To do this, the actuator rides clocked to
the end positions (OPEN or CLOSED).
The corresponding values are contained in the following
table. These values apply for 90° angle. Cycle time without
BCD: 5s for 90° (EA21); 15s for 90° (EA31); 25s for 90° (EA42)
Switch setting
Cycle time monitoring [s]
EA21
EA31
EA42
0
Delivery position
8
20
30
1
12
25
35
2
15
30
40
3
19
35
45
4
25
40
50
5
30
50
55
6
35
60
65
7
35
60
75
The switch positions 8 – 9 have the function of position 7.
The extension of the cycle time is also active in case of failu-
re or reset operation.
Содержание EA21
Страница 33: ...69...
Страница 36: ...72 Notizen Notice Note...