TS 5000 L-E-ISM VPK
Mounting and fixing
GB 8
6.9 Adjusting trigger unit
X
Close fixed leaf.
X
Turn regulating screw
R
until the
triangle on the door closer covers the
marking (
2.
).
X
Tighten lock nut
K
.
X
If the physical conditions are unfavour-
able (e.g. lintel lining bracket mount-
ing), the trigger unit can be set via the
adjustment piece (14).
X
Operate the trigger lever several times
and check if the marker at the shutter
still is congruent. Readjust if necessary.
X
Check, if the wire rope mantle fits the
adjustment piece SF when the fixed leaf
is open.
6.10 Adjusting electrical hold-open device
Moving leaf is shown.
X
Open door leaf to desired hold-open angle and fix it there (
1.
).
X
Remove cable protection foils from guide (
2.
).
X
Loosen clamping screws of electrical hold-open device (
3.
).
X
Move electrical hold-open device until catch contacts sliding block (
4.
).
X
Screw down electrical hold-open device securely (
5.
).
X
To prevent loops from forming, tighten cable and fasten cable protection at hold open device end (
6.
).
X
Stow away (
7.
) loose cable in the cable protection and free area.
X
Secure exposed cable with the cable protection film (
8.
).
CAUTION!
X
Check free upward movement of the rocker!
9.
If necessary, the holding force can be adjusted (
9.
). According to EN 1155, the release torque should
amount to 40 Nm - 120 Nm for a door with 90° hold- open angle.
Fig.: 6.9.1
Fig.: 6.10.1