Technical data
Slimchain 230 V AC
EN 14
13 Technical
data
Slimchain 230 V
Mechanical data
Pulling force [N]
300
Compressive force [N]
200
Stroke length [mm] (see drive identification plate) 200 - 800
Standard ventilation stroke
* parameters can be set
= stroke length*
Stroke speed [mm/sec]
* parameters can be set (3 -7 mm/sec)
Open: 5*
Close: 5*
End position cut-off extended
electronic via internal path sensor
End position cut-off retracted
electronic via path and load
Overload cut-off
electronic via current consumption
Weight [kg]
1.1 - 1.7
Stroke / drive length [mm]
200/478
300/528
500/628
800/778
Electrical data
Voltage [V AC]
230 +/-10%
Frequency [Hz]
47-63
Duty rating [%]
30
Short-term operation [min]
6
Power consumption [W]
30
Current consumption ventilation mode [A] 0.3
Parallel connection drives max.
10
Ambient temperature [°C]
-5 / +70
IP rating [IP] / protection type
IP 30 / II
Area of application
dry rooms
Connection cable/cross-section [mm²]
3 x 0.75, PVC, 80°C
Length of power supply cable [m]
2, optional special length