Safety instructions
1
Safety instructions
1.1 Intended use
The Powerturn/Powerturn F drive unit is designed for the automatic opening and closing of single-action swing doors.
The Powerturn is designed solely for use
à
in dry rooms,
à
in entrances and interior areas of pedestrian traffic in commercial plants and public areas,
à
in private areas.
The Powerturn
à
may be used on escape and rescue routes,
à
must not be used on fire and smoke protection doors,
à
must not be used for potentially explosive areas.
The Powerturn F
à
is designed for use on fire or smoke protection doors,
à
may be used on escape and rescue route doors,
à
must not be used for potentially explosive areas.
Any improper use such as permanent manual operation, as well as any modification to the product, is not permitted.
Observe the “GEZE Product information for door closers”.
1.2 Safety instructions
à
The mandatory installation, maintenance and repair work must be performed by properly trained personnel
authorised by GEZE.
à
The country-specific laws and regulations are to be observed during safety-related tests.
à
If unauthorised changes are made to the system, GEZE cannot be held liable in any way whatsoever for any
resulting damage, and the statement of approval for use in escape and rescue routes is no longer valid.
à
GEZE does not accept any warranty for combinations with third-party products.
à
Furthermore, only original GEZE parts may be used for repair and maintenance work.
à
The connection to the mains voltage must be made by a professional electrician. Perform the power connec-
tion and protective earth connection test in accordance with VDE 0100 Part 610.
à
Use an on-site automatic cut-out as the line-side disconnecting device, the dimensioning of which is matched
to the type, cross-section, type of routing and ambient conditions of the on-site power supply circuit. The au-
tomatic cut-out must have at least 4 A and max. 16 A.
à
Protect the display programme switch against unauthorised access.
à
In compliance with Machinery Directive 2006/42/EC, a risk analysis must be performed and the door system
identified in accordance with CE Marking Directive 93/68/EEC before the door system is commissioned.
à
Observe the latest versions of guidelines, standards and country-specific regulations, in particular:
à
ASR A1.7 “Guidelines for doors and gates”
à
DIN 18650 “Building hardware - Powered pedestrian doors”
à
DIN EN 16005 “Power operated pedestrian doorsets - Safety in use - Requirements and test methods”
à
DIN VDE 0100-600 “Testing electrical systems”
à
DIN EN 60335-2-103, DIN 18263-4
à
Accident prevention regulations, especially DGUV regulation 1 “Principles of prevention” and DGUV regula-
tion 3 “Electrical installations and equipment”
The product should be installed or incorporated in such a way that effortless access to the product is guaranteed
during any repairs and/or maintenance, and that any removal costs do not stand out of economic proportion
to the value of the product.
Содержание Powerturn
Страница 50: ...Powerturn 50 Powerturn installation check list...
Страница 51: ...Powerturn 51 Powerturn installation check list...
Страница 52: ...Powerturn 52 Powerturn installation check list...
Страница 53: ...Powerturn 53 Powerturn installation check list...
Страница 54: ...Powerturn 54 Powerturn installation check list...
Страница 55: ...Powerturn 55 Powerturn installation check list...