11
Parameter
|
Note regarding 2-byte parameter settings:
Depending on the setting of the object type value
there will be new parameters; depending on the
parametrisation the values can be input immediately
or are ascertained via sign x basic value x factor.
- Changing specific parameters via the bus
The following parameters can be modified via the bus:
– "Time factor, staircase timer"
– "Range"
– "Brightness threshold"
|
Note:
Following bus voltage failure and recovery the
modified values will be retained.
Communication objects
You can select the following communication objects:
Block X, general times:
Block X, general movement sensors:
Block X, general brightness:
Parameter
- Master/slave planning via the trigger object or master
trigger object
General information regarding the trigger object and
master trigger object
The trigger object acts on the staircase timer
without
brightness measurement. Object value "1" starts the
staircase timer (start of movement action) while further "1"
telegrams retrigger the staircase timer, if enabled.
Object value "0" can switch the staircase timer off (end of
movement time action), if enabled.
The master trigger object acts on the staircase timer
with
brightness measurement. Object value "1" starts the
staircase timer (start of movement action) while further "1"
telegrams retrigger the staircase timer, if enabled.
Object value "0" has no meaning as regards the master
trigger object.
The parameters "Trigger object observes the safety pause"
(enabled/disabled) and "Master trigger object observes the
safety pause" (enabled/disabled) determine the effect of the
safety pause on the two external trigger objects.
Block X, general
Parameter
Setting
Disable function
Disabled
Enabled
Block X, general - disable function
Parameter
Setting
Activation time point of disable
function
Active during telegram reception
After download / bus voltage
recovery
Block
For object value "1"
For object value "0"
Behaviour at the start of Telegrams
block on Output object 1-4 tab
Do not transmit a telegram
Transmit telegram
Behaviour at the start of Telegrams
block on Output object 1-4 tab (only
visible at master- or monitoring
mode)
Transmit cyclic telegram
Time base
1 s
1 min
1 hr
Time factor (1 - 255)
1 - 255; preconfiguration:
30
Block X general telegrams output
switching/value object X
Parameter
Setting
At start of block
OFF telegram
ON telegram
1 byte 0% - 100%
1 byte 0 - 255
2 bytes floating point or value
Function
Object name
Type
Prio
Flags Behaviour
Block X
Time factor,
staircase timer
1 byte Low
WC
Receive
Function
Object name
Type
Prio
Flags Behaviour
Block X
Range
1 byte Low
WC
Receive
Function
Object name
Type
Prio
Flags Behaviour
Block X
Brightness
threshold
2 bytes Low
WC
Receive
Block X, general times
Parameter
Setting
Time factor staircase timer object
Disabled
Enabled
Block X, general movement
sensors
Parameter
Setting
Range object (for all sensors)
Disabled
Enabled
Block X, general brightness
Parameter
Setting
Brightness threshold object
Disabled
Enabled