10
parameter setting, some functions or objects may or
may not be displayed in the ETS.
Communication objects
Operating mode: Slave mode
|
Note:
No objects for "Time factor" or objects for
"Triggering" are displayed.
Parameter
Operating mode: Slave mode
Communication objects
Operating mode: Monitoring mode
|
Note:
No objects for "Time factor" or objects for
"Triggering" are displayed.
Parameter
Operating mode: Monitoring mode
- Disable function
The movement detector can be disabled with the aid of the
disable object; here the activation time point can be
download / bus voltage recovery or reception of a disable
telegram. The activation telegram for the disable function
can be an ON telegram or an OFF telegram. At the start of
disablement (if enabled via parameter) a telegram can be
sent via the corresponding output object. Cyclic
transmission makes sense with, for example, monitoring
since certain bus devices require a cyclically transmitted
OFF telegram. When the disable function is disabled, the
current status of the movement detector is restored (an
ongoing staircase timer is not stopped/start of movement
actions or action when movement time elapses is
transmitted).
Communication objects
You can select the following communication objects:
Block X, general:
Block X, general times
Parameter
Setting
Master triggering is (brightness-
dependent)
Enabled
Disabled
Via movement/master trigger object,
time is
Retriggerable
Not retriggerable
Master trigger object includes the
safety pause
Enabled
Disabled
Triggering is (not brightness-
dependent)
Enabled
Disabled
Switch off staircase timer via trigger
object
Enabled
Disabled
Via trigger object, time is
Retriggerable
Not retriggerable
Trigger object includes the safety
pause
Enabled
Disabled
Staircase timer adjustable via
Parameters
Potentiometer
Overwriting staircase timer during
download
Enabled
Disabled
Self-adjusting staircase timer (always
retriggerable)
Disabled
Enabled
The following settings are only
visible when "Self-adjusting staircase
timer" is "disabled".
Time factor staircase timer object
Disabled
Enabled
Time base, staircase timer
1 min
1 s
1 hr
Time factor for staircase timer (1 -
255)
1 - 255; preconfiguration:
25
The following settings are only
visible when "Self-adjusting staircase
timer" is "enabled".
Minimum time factor (1 - 255)
Staircase timer
1 - 255; preconfiguration:
5
Time factor for learning step (1 - 255)
Staircase timer
1 - 255; preconfiguration:
1
Maximum time factor (1 - 255)
Staircase timer
1 - 255; preconfiguration:
25
Sensitivity of learning step
1 - 5; preconfiguration:
4
1 = slow
5 = sensitive
Block X, general times
Parameter
Setting
Cyclic interval during movement
Time base
1 min
1 s
1 hr
Time factor (1 - 255)
1 - 255; preconfiguration:
5
Block X, general times
Parameter
Setting
Cyclic interval during movement
Time base
1 s
1 min
1 hr
Time factor (1 - 255)
1 - 255; preconfiguration:
5
Cyclic interval when movement time
has elapsed
Time base
1 s
1 min
1 hr
Time factor (1 - 255)
1 - 255; preconfiguration:
5
Function
Object name
Type
Prio
Flags Behaviour
Block X
Disable object
1 bit
Low
WC
Receive