USER INSTRUCTIONS
60
When the bus power supply fails, the device performs no actions. The time and date are
maintained by the buffer power system (batteries) whilst all the other settings are saved
to a non-volatile memory.
The device is in full operating mode within a maximum of 5 seconds from reinstatement
of the bus power supply
If the buffer power (battery) is absent, the timer-thermostat will restart in OFF mode when
the bus power is reinstated.
Day of the week
1:Monday
Hour
00:00
Heating temperature set-point
T
FROSTPROTECT
16 °C
18 °C
20 °C
5 °C
Air-conditioning temperature set-point
T
HIGH TEMPERATURES PROTECTION
24 °C
26 °C
28 °C
35 °C
Self-learning
OFF
Differential regulation
Heating
Air conditioning
0.2 °C
0.5 °C
Temperature unit of measurement
°C
Preset parameters
Behaviour on the failure and
reinstatement of the bus power supply