P05 - setting the ON/OFF regulation differential
When the
, symbol appears, set the differential
regulation value using the
keys.
Press the
key within 30 seconds to confirm the value
set.
The regulation differential is the deviance between the
set-point setting and the actual activation temperature.
It is possible to set different regulation differentials for the
heating and air-conditioning functions. It is recommended
to retain the preset values except in special situations.
P06 - Control logic
When the P06 code appears on the screen, set the
thermal regulation control logic using the
keys.
(00 = 2 point control, 01 = proportional control
(PWM))
Press the
key within 30 seconds to confirm the value
set.
It is possible to set different control logics for the heating
and air-conditioning functions.
If you select a 2 point control, move on to point P09, for
proportional control move on to point P07.
2 POINT CONTROL
The thermal regulation plant is disabled when:
the temperature is equal to the set point and reactivated
when:
- the temperature is equal to or lower than the set point
-
for heating;
- the temperature is equal to or higher than the set point
+
for air-conditioning;
The diagrams below show the two function types.
USER INSTRUCTIONS
49